PowerFlex® 700L Frame 2 Common Mode Choke Kit
3
Figure 1 Power Wiring Connections Through Choke Assemblies to the Drive
Figure 2 Motor Output Power Leads through Choke Assembly
8. Mount the choke assembly for the AC input power to the drive on a metal
surface near the bottom of the drive using M8 hardware. Leave sufficient
clearance between the choke assembly and the drive terminals to allow
access to the terminals and provide proper bend radius for the leads.
9. Run the AC input power leads to the drive straight through the choke
assembly (
) and terminate at the R/L1, S/L2, and T/L3 drive
terminals. Note: When using multiple conductors for each phase, pass all
conductors through the same choke assembly.
AC Input
POWER
STS
PORT
MOD
NET A
NET B
Motor
Choke
Assembly
PE
W/T3
V/T2
U/T1
Choke
Assembly
T/L3
S/L2
R/L1
Ground
Motor Frame
To Motor W (T3)
To Motor V (T2)
To Motor U (T1)
From Drive W (T3)
From Drive V (T2)
From Drive U (T1)