Power terminal block – Rockwell Automation 20A PowerFlex 70 Adjustable Frequency AC Drive User Manual
Page 20

20
Rockwell Automation Publication 20A-IN009D-EN-P - June 2013
PowerFlex 70 Adjustable Frequency AC Drive
Power Terminal Block
Figure 7 - Typical Power Terminal Block Location (B frame shown)
Table 5 - Power Terminal Block Specifications
Table 6 - Wire Routing Recommendations
No.
Name
Frame
Description
Wire Size Range
(1)
(1) Maximum/minimum sizes that the terminal block can accept – these are not recommendations.
Torque
Max
mm
2
(AWG)
Min
mm
2
(AWG)
Max
N•m (lb•in)
Recommended
N•m (lb•in)
➊
Power
terminal block
A, B, C
Input power and
motor
connections
4.0 (10)
0.3 (22)
1.1 (10)
0.8 (7)
D
Input power and
motor
connections
10.0 (6)
0.8 (18)
1.7 (15)
1.4 (12)
E
Input power and
motor
connections
25.0 (3)
2.5 (14)
2.71 (24)
2.71 (24)
➋
SHLD terminal
All
Terminating
point for wiring
shields
—
—
1.6 (14)
1.6 (14)
No.
Description
➌
Suggested entry for incoming line wiring.
➍
Suggested entry for motor wiring.
IP 20 (NEMA/UL Type 1)
IP 66 (NEMA/UL Type 4X/12)