Wiring diagrams – Rockwell Automation 40CA4 Miniature End View Transmitted Beam Control User Manual

Page 2

Advertising
background image

INSTALLATION

The control must be securely mounted on a firm, stable surface or

support. A mounting which is subject to excessive vibration or shift-
ing may cause intermittent operation.

DIMENSIONS

1"

(25.4)

NO. (60Ć1711) EXTENDED

LENDS ACCESSORY (IF

USED)

1

/

4

-18NPSM

VISIBLE LED

ALIGNMENT AND

OPERATION

INDICATOR ON

40CA4

13/64 O.D. (5.16)

P.V.C. JACKETED

CABLE

11/16

(17.5)

1ă17/32

(38.9)

2ă27/32

(72.2)

5/8

(15.9)

13/16

(20.6)

9/16

(14.3)

61/64

(24.1)

57/64

(22.6)

WIRING

All external wiring should conform to the National Electric Code

and applicable local codes. See wiring diagrams for external connec-
tions. For maximum electric shielding, rigid conduit is recommended
for extensions of scanner wiring. DO NOT RUN PHOTODETEC-
TOR WIRES AND LINE VOLTAGES IN THE SAME CONDUIT.

WIRING DIAGRAMS

1

2

3

4

PLUGĆIN

CONTROL MODULE

22 SERIES 4000

CONTROL BASE

47CN4 AND 47SN1

RECEIVERS

40CA4 AND 40SA1

LED SOURCES

WHT

RED

RED

BLK

SH

SH

GROUND THIS

TERMINAL

Notes:

1. Ground receiver housing (machine ground O.K.)

2.Ground terminal 4.

WIRING DIAGRAMS

OPEN COLLECTOR (NPN) CURRENT SINK

OUTPUT TO POWER EXTERNAL LOADS

OR TO #61-2124 OUTPUT BASE

L1

L2

OUT

1

2
3

SERIES

5000

#60–2120 BASE

120VAC

RECEIVER

LED SOURCE

BLK

RED

RED

WHT

CONNECT ALL SHIELDS TO TERMINAL PS (-)

PS( -)

WITH UNIVERSAL FUNCTION BASE #60–2120

OUT

1
2

3

PS (-)

SERIES

5000

PS (+)

PS (-)

OUT

1

( + )

( - )

24VDC

#60-2123

OPEN COLLECTOR (NPN) CURRENT SINK

OUTPUT TO POWER EXTERNAL LOADS

OR TO #61-2124 OUTPUT BASE

OUTPUT

RECEIVER

BLK

RED

#60–2123 BASE

CONNECT ALL SHIELDS TO TERMINAL PS (-)

RED

WHT

LED SOURCE

WITH MULT–MODULE FUNCTION BASE #60–2123

ALIGNMENT

Set the amplifier to the light operate mode. Adjust the sensitivity

to the maximum setting, turning the sensitivity potentiometer clock-
wise. Aim the light source at the receiver until the alignment indicator
on the amplifier turns on.

To be certain that the beam is centered, sweep the receiver at the

light source in the horizontal plane and determine the position where
the alignment indicator turns on and then off. Do the same in the verti-
cal plane. Set the beam halfway between both positions.

It may be necessary to reduce the sensitivity to a lower setting for

transparent or translucent materials or to detect objects smaller that
the effective beam.

Publication PA–9200(A)

November 1992

Supercedes Publication PA–7913

Advertising