Publication 280GS-QS001A-EN-P - May 2009

Wiring

Power, Control, Safety Monitor Inputs, and Ground Wiring

Table 1 provides the power, control, safety monitor inputs ground wire
capacity, and the tightening torque requirements. The power, control, and
ground terminals will accept a maximum of two wires per terminal.

Table 1

Power, Control, Safety Monitor Inputs, Ground Wire Size, and Torque

Specifications

Terminal Designations

As shown in Figure 3, the ArmorStart Distributed Motor Controller contains
terminals for power, control, safety monitor inputs, and ground wiring.
Access can be gained by removing the terminal access cover plate.

Figure 3 ArmorStart Power, Control, Safety Monitor Inputs, and Ground Terminals

Table 2

Power, Control, and Ground Terminal Designations

Terminals

Wire Size

Torque

Wire Strip Length

Three-phase

Power

and

Ground

Primary/Secondary

Terminal:

1.5…4.0 mm

2

(#16 …#10 AWG)

Primary Terminal:

10.8 lb•in. (1.2 N•m)

Secondary Terminal:

4.5 lb•in (0.5 N•m)

0.35 in. (9 mm)

Control Power and

Safety Monitor Inputs

1.0…4.0 mm

2

(#18…#10 AWG)

6.2 lb•in (0.7 N•m)

0.35 in. (9 mm)

Terminal Designations

No. of Poles

Description

SM1

2

Safety I/O Input

SM2

2

Safety I/O Input

A1 (+)

2

Control Power Input

A2 (-)

2

Control Power Common

PE

2

Ground

1/L1

2

Line Power Phase A

3/L3

2

Line Power Phase B

5/L5

2

Line Power Phase C