Misalignment curve, Wiring diagram, Diagnostic – Rockwell Automation 440N SensaGuard 18 mm Stainless Steel Barrel Unique Coded Installation Instructions User Manual

Page 5: Sensaguard

Advertising
background image

PN-46046 10000054880 Ver 00 October 2009

Misalignment Curve

18 mm Unit with 18 mm Target

Note: There must be a minimum spacing of 4 mm (0.157 in) if actuator and sensor face approaches
laterally. This will prevent false triggering due to the side lobe areas.

Wiring Diagram

Pin #

Wire Color

Signal

1

White

Aux Outputs

2

Brown

+24V

3

Green

Sheild

4

Yellow

OSSD 2, +24V Input

5

Grey

OSSD 1

6

Pink

OSSD 2

7

Blue

0V

8

Red

OSSD 1, +24V Input

Recommended mating cable, 2 m (6.5 ft). 889D-F8AB-2. Lengths are available up to 30 m (98.4 ft)

Diagnostic

Unit Indicators (per IEC 60073)

State

Status

Troubleshooting

Off

Not Powered

NA

Device Output

Red

Not Safe, OSSD not active

NA

LED

Green

Safe, OSSD active

NA

Green flash

Power up test or OSSD

Check 24V DC or OSSD inputs

inputs not valid

(yellow and red wire)

Red Flash

1 Hz Flash Recoverable Fault

Recoverable fault —check OSSD

4 Hz Flash Non-recoverable Fault

outputs are not shorted to GND,

24V DC or each other. Cycle power.

SensaGuard

TM

18 mm Stainless Steel Barrel Installation Instructions 5

Misalignment

Sensing Distance

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

-15-14-13-12-11-10-9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Side Lobe

Side Lobe

Assured Sensing

Distance

OFF

OFF

OFF

ON

4

7

6

8

1

5

2

3

Brown

White

Blue

Pink

Grey

Green

Red

Yellow

Note: Refer to Technical Specifications for Certification information and ratings.