Chapter 2 Installation
Figure 18 - Current Transformer Connection to Converter Module
➊ Another current transformer connects L2 and T2, and another connects L3 and T3.
➋ The converter module, Cat No. 825-MCM20, must be used in these applications.
Table 9 - SMC-50 Conductor and Torque Requirements
L1
L2
L3
T1
T2
T3
Current Transformer ➊
Converter Module➋
SMC-50
Cat. No.
Lug Kit
Cat. No.
Wire Strip
Length [mm]
Conductor Range
Max. No. Lugs Pole
Torque
Bypass Bus
Kit Cat. No.
Line Side
Load Side
Wire-Lug
Lug-Bus
150-SB…
1494R-N14
Long = 44.5
Short = 22.4
54…120 mm
2
(1/0…250 MCM)
1
1
31 N•m
(275 lb•in.)
23 N•m
(200 lb•in.)
—
150-SC…
199-LF1
18…20
16…120 mm
2
(#6…250 MCM)
2
2
31 N•m
(275 lb•in.)
23 N•m
(200 lb•in.)
150-SCBK
150-SD…
199-LG1
18…25
25…240 mm
2
(#4…500 MCM)
2
2
42 N•m
(375 lb•in.)
28 N•m
(250 lb•in.)
150-SDBK