Program Group Parameters

(continued)

No.

Parameter Name

Min/Max Range Units/Settings

Default

44

[DC Hold Time]

0-25

0.1 Sec.

0

45

[DC Hold Voltage]

0-115

1 Volt

0

46

[Input Mode]

0-6

0 = 3 wire control

0

1 = 2 wire control
2 = Keypad control
3 = Momentary FWD/REV control
4 = 2 wire “Accel/Decel” control
5 = 2 wire “Enable” control
6 = 2 wire “Local/Remote” control

47

[Output Configure]

0-9

0 = Controller Ready/Faulted 0
1 = At Frequency
2 = Controller Running
3 = Reverse
4 = Motor Overload
5 = Ramp Regulated
6 = Above Frequency
7 = Above Current
8 = Above DC Bus Voltage
9 = Retries Exhausted

48

[Output Threshold]

0-815

P47 = 6 = 0-240 Hz Range

0

P47 = 7 = 0-180% Range
P47 = 8 = 0-815 V Range

49

[PWM Freq.]

2.0-8.0

0.1 kHz

4.0

50

[Restart Tries]

0-9

Numeric Value

0

51

[Restart Time]

0.5-300

0.1 Sec.

10.0

52

[DB Enable]

0-100

0 = Disable, > 0 = % of dB

0

53

[S-Curve]

0-10

0, 1...10 @ 10% Increments 0

54

[Clear Fault]

0-1

1 = Reset fault

0

55

[Memory Probe Address] Numeric Value

Numeric Value

Numeric

56

[Reset Functions]

0-2

0 = Idle Status

0

1 = Reset Defaults
2 = Update Input Mode

57

[Program Lock]

0-1

1 = Lock

0

0 = Unlock

58

[Internal Freq.]

0-240

0.1 Hz

60

59

[Freq. Select]

0-1

0 = TB3

0

1 = Internal Freq. Source

60

[Zero Offset]

–50.0 to +50.0

0.1%

0

61-68 [Preset Freq.0 – 7]

0-240

0.1 Hz

See Below

69

[Accel Time 2]

0.0-600

0.1 Sec.

20.0

70

[Decel Time 2]

0.1-600

0.1 Sec.

20.0

71

[IR Compensation]

0-150

1%

50%

72

[Slip Compensation]

0.0-5.0

0.1 Hz

2.0 Hz

73

[Reverse Disable]

0-1

0= Enable

0

1= Disable

74

[Analog Select]

0-1

0= Unipolar

0

1= Bipolar

75

[Analog Input Min.]

0.0-150.0

0.1%

0.0%

76

[Analog Input Max.]

0.0-150.0

0.1%

100%

77

Not Used

78

[Compensation]

0-1

Numeric Value

0

This parameter applies to the Preset Speed model only.

When using P46, [Input Mode] setting “4,” the Accel and Decel times are selected
by providing an input to TB3-8.

3

2

1

TB3

4

5

6

7

8

9

10

11

Name
[Preset 0]
[Preset 1]
[Preset 2]
[Preset 3]
[Preset 4]
[Preset 5]
[Preset 6]
[Preset 7]

Default
3 Hz
20 Hz
30 Hz
40 Hz
45 Hz
50 Hz
55 Hz
60 Hz

Accel

Parameter 30,
[Accel Time 1]

Parameter 69,
[Accel Time 2]

Decel

Parameter 31,
[Decel Time 1]

Parameter 70,
[Decel Time 2]

SW2
0
0
1
1
0
0
1
1

No.
61
62
63
64
65
66
67
68

SW1
0
1
0
1
0
1
0
1

SW3
0
0
0
0
1
1
1
1

Display Group Parameters
No.

Parameter Name

Min/Max Range

Units/Settings

01

[Output Frequency]

0-240 Hz

0.1 Hz

02

[Output Voltage]

0-[Max Voltage]

1 Volt

03

[Output Current]

0-2 x Rtd. Out. Curr. 0.01Amps

04

[Output Power]

0-2 x Rtd. Out. Power 0.01 kW

05

[Bus Voltage]

0-400 (230V)

1 Volt

0-800 (460V)

06

[Frequency Command] 0-240

0.1 Hz

07

[Last Fault]

0-49

Numeric Value

08

[Heatsink Temperature] 0-150

1 Degree C.

09

[Controller Status]

0000 to 1011

Bit 3

Bit 2

Bit 1

Bit 0

Decel Accel Forward

Running

10

[Controller Type]

Numeric Value

Numeric Value

11

[Control Version]

Fixed Value

Numeric Value

12

[Input Status]

0000 to 1111

See Below

13

[Power Factor Angle]

0.0-180.0

0.1 Degrees

14

[Memory Probe Display] Numeric Value

Numeric Value

15

[Preset Status]

0000 to 0111

Bit 3

Bit 2

Bit 1

Bit 0

Not Used SW3

SW2

SW1

16

[Analog Input]

–150 to +150

0.1%

Program Group Parameters
No.

Parameter Name

Min/Max Range Units/Settings

Default

30

[Accel Time 1]

0.0-600

0.1 Sec.

10.0

31

[Decel Time 1]

0.1-600

0.1 Sec.

10.0

32

[Min. Freq.]

0-240

1 Hz

0

33

[Max. Freq.]

0-240

1 Hz

60

34

[Stop Mode Select]

0-3

0 = Ramp

0

1 = Coast
2 = DC Brake
3 = DC Brake Auto-Off

35

[Base Freq.]

10-240

1 Hz

60

36

[Base Voltage]

20-230/460

1 Volt

230/460

37

[Max. Voltage]

20-255/510

1 Volt

230/460

38

[Boost Select]

0-12

Start Volts (%) Midpoint (%) 2
0 = 0

9 = 45.0

1 = 2.5

10 = 40.0

2 = 5.0

11 = 35.0

3 = 7.5

12 = 30.0

4 = 10.0
5 = 12.5
6 = 15.0
7 = 17.5
8 = 20.0

39

[Skip Freq.]

0-240

1 Hz

240

40

[Skip Freq. Band]

0-30

1 Hz

0

41

[Motor Overload Select] 0-2

0 = No Derating

0

1 = Min. Derating
2 = Max. Derating

42

[Motor Overload Current] 0.1-200% of

0.01 Amps

115% of

Controller Rating

Rating

43

[Current Limit]

1-180% of

1 %

150%

Controller rating

1

TB3

2

3

4

5

6

7

8

9

10

11

Description
3 Wire
2 Wire
Keypad
Mom. Run Fwd/Rev
Accel/Decel

Enable

Local/Remote

Bit 3
0 = Positive
Analog Input

1 = Negative
Analog Input

Bit 1
Stop
Stop
Stop
Stop
0=Accel 2/Decel 2
1=Accel1/Decel 1
0=Drive Disable
1=Drive Enable
0=Local (TB3) Control
1=Remote Control

Input
Mode
0
1
2
3
4

5

6

Bit 2
Start
Run Forward
N/A
Run Forward
Run Forward

Run Forward

Run Forward

Bit 0
Reverse
Run Reverse
N/A
Run Reverse
Run Reverse

Run Reverse

Run Reverse

160 Parameter List

Programming Steps

1. To program the value of a Program

Group parameter, enter the program
group by pressing the ESCape key.
The Program Mode Indicator will illu-
minate.

2. Press the Up/Down Arrow keys until

the desired parameter number is dis-
played.

3. Press the SELect key. The Program

Mode Indicator flashes, indicating that
you can use the Up/Down Arrow keys
to change the parameter value.

4. Press the arrow keys until the desired

value is shown.

Important: Continuously holding the
Up or Down key will cause the value
to increase or decrease as long as the
key is pressed.

5. When the desired value is displayed,

press the Enter key. This writes the
new value to memory. The Program
Mode Indicator will stop flashing and
the display will flash once indicating
that the new value has been accepted.

Important: If at any time (while in
the Program mode) you wish to abort
the editing process, press the ESCape
key. The original value of the parame-
ter will remain unchanged and you
will be exited from the Program
Mode.

Action

Description