Indicator status for interface module – Rockwell Automation 440R-ENETR Guardmaster EtherNet/IP Network Interface - Installation Instructions User Manual
Page 15

Guardmaster® EtherNet/IP™ Network Interface 15
Publication 440R-IN078A-EN-P - January 2014
Network
Status
Off
Device is not on-line:
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator
Flashing green
Device is on-line but has no CIP connections in the
established state.
Solid green
Device on-line and has CIP connections in the established
state.
Flashing red
One or more CIP connections in timed-out state. Check for
Guardmaster safety relay failure and controller operation.
Solid red
Duplicate IP address detected.
Verify IP address setting and correct, as needed.
Link 1 or
Link 2
Status
Off
No link established.
Solid green
One of the following conditions exists:
- A 100 Mbps (full or half duplex) link exists.
- The ring network is operating normally.
Flashing green
Transmit or receive activity present on indicated port @
100 Mbps.
Solid yellow
One of the following conditions exists:
- A 10 Mbps (full or half duplex) link exists.
- The ring network is operating normally.
Flashing yellow
Transmit or receive activity present on indicated port @
10 Mbps.
Indicator Status for Interface Module