Wiring
Power, Control, Safety Monitor Inputs, and Ground Wiring
Table 1 provides the power, control, ground wire capacity, and the
tightening torque requirements. The power, control, and ground terminals
will accept a maximum of two wires per terminal.
Table 1
Power, Control, Safety Monitor Inputs, Ground Wire Size, and Torque
Specifications
Terminal Designations
As shown in Figure 2, the ArmorStart Distributed Motor Controller contains
terminals for power, control, and ground wiring. Access can be gained by
removing the terminal access cover plate.
Figure 2 ArmorStart Power, Control, and Ground Terminals
Table 2
Power, Control, and Ground Terminal Designations
Terminals
Wire Size
Torque
Wire Strip Length
Three-phase
Power
and
Ground
Primary/Secondary
Terminal:
1.5…4.0 mm
2
(#16 …#10 AWG)
Primary Terminal:
10.8 lb•in. (1.2 N•m)
Secondary Terminal:
4.5 lb•in (0.5 N•m)
0.35 in. (9 mm)
Control Power
1.0…4.0 mm
2
(#18…#10 AWG)
6.2 lb•in (0.7 N•m)
0.35 in. (9 mm)
Terminal Designations
No. of Poles
Description
A1 (+)
2
Control Power Input
A2 (-)
2
Control Power Common
PE
2
Ground
1/L1
2
Line Power Phase A
3/L3
2
Line Power Phase B
5/L5
2
Line Power Phase C