Power Wiring

Refer to the product nameplate or the SMC Flex User Manual for device specific information.

Control Terminals

SMC Rating

[A]

Lug Kit

Cat. No.

Wire Strip

Length

Conductor

Range

Max. No. Lugs/Pole

Tightening Torque

Line Side

Load Side

Wire - Lug

Lug - Busbar

5…85

—

18…20 mm

2.5…85 mm

2

(#14…3/0 AWG)

—

—

11.3 N•m

(100 lb•in)

—

108…135

199-LF1

18…20 mm

16…120 mm

2

(#6…250 MCM)

1

1

31 N•m

(275 lb•in)

23 N•m

(200 lb•in)

201…251

199-LF1

18…20 mm

16…120 mm

2

(#6…250 MCM)

2

2

31 N•m

(275 lb•in)

23 N•m

(200 lb•in)

317…480

199-LG1

18…25 mm

25…240 mm

2

(#4…500 MCM)

2

2

42 N•m

(375 lb•in)

28 N•m

(250 lb•in)

625…780

100-DL630

32 mm/64 mm

70…240 mm

2

(2/0…500 MCM)

2

2

45 N•m

(400 lb•in)

68 N•m

(600 lb•in)

970

100-DL860

26 mm/48 mm

120…240 mm

2

(4/0…500 MCM)

1

1

45 N•m

(400 lb•in)

68 N•m

(600 lb•in)

1250

100-DL630

32 mm/64 mm

70…240 mm

2

(2/0…500 MCM)

1

1

45 N•m

(400 lb•in)

68 N•m

(600 lb•in)

100-DL860

26 mm/48 mm

120…240 mm

2

(4/0…500 MCM)

1

1

Terminal

Description

Terminal

Description

Footnotes

11

➂➃

Control Power Input (+)

23

➀

PTC Input

➀

Do not connect any additional loads to these
terminals. These “parasitic” loads may cause
incorrect operation.

➁

When set for External Bypass mode, the SMC
Flex can be used to control a properly sized
external contactor and overload once the motor
reaches full speed. The SMC-Flex overload
functionality is disabled in this mode.

➂

RC Snubbers are required on inductive type
loads connected to auxiliary contacts.

➃

Control power on units rated 625…1250 A is
pre-wired internally, from terminal block CP1.

12

➂➃

Control Power Common

24

➀

PTC Input

13

➀

Controller Enable Input

25

Tachometer Input

14

Ground

26

Tachometer Input

15

➀➂

Option Input #2

27

➀

Ground Fault Transformer Input

16

➀➂

Option Input #1

28

➀

Ground Fault Transformer Input

17

➀➂

Start Input

29

➁➂

Aux Contact #2

18

➀➂

Stop Input

30

➁➂

Aux Contact #2

19

➁➂

Aux Contact #1

31

➁➂

Aux Contact #3

20

➁➂

Aux Contact #1

32

➁➂

Aux Contact #3

21

Not Used

33

➁➂

Aux Contact #4

22

Not Used

34

➁➂

Aux Contact #4

23 24 25 26 27 28 29

30 31 32 33 34

11 12 13 14 15 16 17

18 19 20 21 22