Rockwell Automation 140U Q, M frame CB Electronic RMS Trip Unit installation and operation User Manual
Page 13

Table 1-1. Electronic RMS Trip Units
3 Pole
Electronic RMS Trip Unit type Catalog Numbers
Trip Unit Functions
LS
LSI
LSG
LSIG
Long Delay Fixed Ampere
Rating
¬ with
Fixed Long Delay
Adjustable ampere
Setting with fixed
Long Delay
l
l
l
l
l
l
l
l
Short Delay Adjustable Short
Delay Pick-up with
Short Delay Time
l
2
t Ramp
Adjustable Short
Delay Time
® with
Adjustable Short
Delay Pick-up, or
Adjustable
Instantaneous
Pick-up
®
l
l
l
l
l
l
Instant Fixed
Instantaneous
(Override)
¯
l
l
l
l
Ground Adjustable Ground
Fault Fault Pick-up with
Adjustable Ground
Fault Time
l
l
Fourth 100% rating for
Pole fourth pole
Protection
60% rating for
fourth pole
Fourth pole
unprotected
¬
Fixed rating plugs available, see Table 1-2
Optional four-setting adjustable rating plugs available, see Table 1-2
® Using trip unit with adjustable short delay time (LSI, LSIG), instantaneous pick-up is achieved when the lowest time delay setting
(1) is selected.
¯ A non-adjustable override setting is set at the frame withstand rating.
Page 13
40752-072(2)
Effective 6/02