Rockwell Automation 871F Proximity Sensors Installation Instructions User Manual

Installation instructions 871f proximity sensors, General specifications

Advertising
background image

Installation Instructions

871F Proximity Sensors

IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE.

871F for Hazardous Locations

Models to be covered:

Conduit 1/2 inch NPT

871F-P50BP80-T4
871F-P50BN80-T4
871F-N65BP80-T4
871F-N65BN80-T4

Conduit PG13.5

871F-P50BP80-Q4
871F-P50BN80-Q4
871F-N65BP80-Q4
871F-N65BN80-Q4

WARNING

Suitable for use in Class 1, Division 2,
Groups A, B, C, D or nonhazardous
locations only.
Explosion hazard: substitution of
components may impair suitability for
Class 1, Division 2.
Explosion hazard: Do not disconnect
equipment unless power has been
switched off or the area is known to be
nonhazardous.

General Specifications

Environmental

Certifications

cULus Listed and CE Marked for all
applicable directives

Enclosure Type Rating

NEMA 1, 2, 3, 4, 6, 6P, 12, and 13, IP67 (IEC
60529), 1200 psi (8270 kPa) washdown;
micro connector versions also meet IP69K
(IEC 60529)

Operating Temperature [C (F)] -25…+70° (-13…+158°)

Electrical

Load Current

≤200 mA

Load Current, Min.

1 mA

Leakage Current

≤10 μA

Operating Voltage

10…30V DC

Voltage Drop

≤2.5V

Repeatability

≤2%

Hysteresis

≤5% typical

Protection Type

False pulse, transient noise, reverse
polarity, short circuit, overload

Shock

30 g, 11 ms

Vibration

55 Hz, 1 mm amplitude, 3 planes

Optical

LEDs

Green: Power
Orange: Output Energized

Mechanical

Housing Material

Valox®

Connection Types

Conduit Opening: 1/2-14 NPT thread,
PG13.5 thread