Wiring diagram input specifications – Rockwell Automation 193-EIMD60 Bul 193 Input Interface Module User Manual

Page 2

Advertising
background image

PN-154475

DIR 10000279788 (Version 00)

Copyright © 2012 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.

WARNING: Be careful when stripping wires. Wire fragments that fall into the module could cause damage at power up. Once wiring is complete, ensure the module is free of all metal fragments. For reliable
input signal processing, input wiring shall be routed in raceways separate from power cabling. For distances exceeding 200 M (656 Ft), the use of shielded cable is recommended.

Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Wiring Diagram

Input Specifications

Basic wiring of input devices is shown below.

Commons are connected internally.

IN 1

1

2

3

4

5

6

IN 2

IN 3

IN 4

EGND

AC

COM

AC

COM

EIMD = 110/120 V ac 50/60 Hz

EIMD60 = 120 V ac 60 Hz

L1

L2

Voltage Category

Catalog Number

110V / 120V ac

Operating Voltage Range

79V ac to 132V ac

Frequency Range

47 Hz to 63 Hz

Number of Inputs

4

Heat Dissipation

0.10 W per input

Signal Delay (max.)

On Delay: 30 ms
Off Delay: 30 ms

Off-State Voltage (max.)

20V ac

Off-State Current (max.)

1.0 mA

On-State Voltage (min.)

79V ac

On-State Current

2.0 mA at 79V ac (min.)
10.0 mA at 132V ac (max.)

Inrush Current (max.)

150 mA

Nominal Impedance

28k ohm at 50 Hz
21k ohm at 60 Hz

IEC Input Compatibility

Type 1

120V ac

193-EIMD

193-EIMD60

79V ac to 132V ac

57 Hz to 63 Hz

4

0.10 W per input

On Delay: 30 ms
Off Delay: 30 ms

20V ac

1.0 mA

79V ac

2.0 mA at 79V ac (min.)
10.0 mA at 132V ac (max.)

150 mA

21k ohm at 60 Hz

Type 1