Installation, Dimensions — mm (inches) – Rockwell Automation 871L DC Limit Switch Style Inductive User Manual

Page 2

Advertising
background image

Installation

Alignment

When power is applied to the sensor, the green (power on)
indicator will turn on. Visually sight the sensing head at the
object to be detected until the red LED starts to blink. This
indicates that the switch is approaching the switching point.
When the red LED is turns off, you are at a reliable margin.
The orange LED (output energized) will then turn on when the
sensor is set for normally open or turn off when the sensor is
set for normally closed.

Sensor (Top View)

Target

Orange

Red

Output Energized

Alignment Aid

Green

Power

Rotation of Sensing Head

Insert screwdriver in slot located at the bottom of the clear
plastic cover, gently pull upward. This will release the locking
mechanism and enable rotation of the sensing head. The
sensing head can be rotated in 15

°

increments.

Locking

Mechanism

Sensing Head Position

Unlock plastic cover and rotate sensing head so that clips are
in the top position. To change from side sensing to top
sensing, simply snap back the two clips located on either side
of the sensing head. Release and rotate the head to the top or
side position, return clips to locking position to secure head.

Clips Must be in

Top Posititon

Selecting Output

Insert screwdriver in slot located at the bottom of the clear
plastic cover, gently pull upward. This will release the locking
clip and allow access to the selectable output. The switch is
supplied in the normally open position. Simply move the
switch to the normally closed position; re-wiring is not
necessary.

(N.C.)

(N.O.)

Locking

Mechanism

Wiring of Terminal Base

Unlock the plastic cover to access the black bar. To release
the base, simply lift the black bar located inside the body. This
will release the locking mechanism. Gently pull the terminal
base from the sensor body to access the screw terminals.

Note: All external wiring should conform to the National Electric

Code and applicable local codes. See wiring diagrams
for external connections.

Black Bar

Dimensions — mm (inches)

120.0

(4.72)

40.0

(1.57)

40.0

(1.57)

60.0

(2.36)

7.3

(0.29)

Conduit

Entrance

1/2-14 NPT

15.9

(0.63)

30.0

(1.18)

LEDs

17.0

(0.67)

30.0

(1.18)

7/8Ć16UNĆ2A

Conduit Style

30.0

(1.18)

M12 x 1

Micro Style

Quick-Disconnect

Mini Style

Quick-Disconnect

Publication 46803–055–01(A)

November 1994

Printed in USA

Advertising