Rockwell Automation 871L AC/DC Limit Switch Style Inductive User Manual

Rockwell Automation Equipment

Advertising
background image

INSTALLATION INSTRUCTIONS

BULLETIN 871L AC/DC LIMIT SWITCH STYLE INDUCTIVE PROXIMITY SENSOR

Nominal Sensing

Distance

Output

Switching

Frequency

Part Number

Head Size

Distance

mm (inches)

Shielded

Output

Configuration

Frequency

(Hz)

Conduit Opening

Mini Style QD

Micro Style QD

40

20 (0.79)

Y

Programmable

15

871L-B20E40-T2

871L-B20E40-N3

871L-B20E40-R3

40

40 (1.57)

N

Programmable

N.O. or N.C.

15

871L-B40E40-T2

871L-B40E40-N3

871L-B40E40-R3

Specifications

Load Current 400mA

Minimum Load Current 2mA

Leakage Current

2mA

Operating Voltage 20Ć250V AC/DC

Voltage Drop

5V

Repeatability

5

%

Hysteresis

20%

False Pulse Protection Incorporated

Transient Noise Protection Incorporated

Short Circuit Protection Incorporated

Overload Protection Incorporated

Enclosure NEMA 3, 4, 6, 12 and 13

IP67 (IEC 529) Polyloy

Connections Conduit Opening:

1/2Ć14 NPT internal

thread with screw

terminals

Quick Disconnect:

3Ćpin mini style

3Ćpin micro style

2 LEDs Green:

Power (Blinks in SCP/Overload)

Orange:

Output Energized

Operating Temperature -25

°

C to +70

°

C (-13

°

F to +158

°

F)

Shock and Vibration 30G, 10Ć55Hz

Correction Factors

Target Material

Correction Factor

Steel

1.0

Stainless Steel

0.90

Brass

0.50

Aluminum

0.45

Copper

0.40

Description

Bulletin 871L inductive proximity sensors are self-contained,
general purpose, solid state devices. These devices are
designed for most industrial applications where it is required to
sense the presence of metal objects (ferrous and non-ferrous)
without touching them.

The 871L limit switch style provides mounting
interchangeability, easy to wire terminations, rugged
construction, and superior sealing. The 25 (twenty-five)
position sensing head allows for twenty-four side views and
one top view.

Diagnostics

Green on indicates power on.
Orange on indicates output is energized.
Green flashing indicates short circuit or overload.

Accessories

Optional Mating Cables

Part Number

Length

Description

871A-CS3-R2

2M (6.56 ft.)

3Ćpin, microĆstyle straight

871A-CS3-R4

4M (13.1 ft.)

3Ćpin, microĆstyle straight

871A-CS3-R5

5M (16.4 ft.)

3Ćpin, microĆstyle straight

871A-CS3-N1

1M (3.28 ft.)

3Ćpin, miniĆstyle straight

871A-CS3-N2

2M (6.56 ft.)

3Ćpin, miniĆstyle straight

871A-CS3-N4

4M (13.1 ft.)

3Ćpin, miniĆstyle straight

871A-CRL3-N1

1M (3.28 ft.)

3Ćpin, miniĆstyle right angle LED

871A-CRL3-N2

2M (6.56 ft.)

3Ćpin, miniĆstyle right angle LED

871A-CRL3-N4

4M (13.1 ft.)

3Ćpin, miniĆstyle right angle LED

Wiring Diagrams

Load

T1

T2

Normally Open

Load

T1

Note: Load can be switched to terminal 1.

T2

Normally Closed

Conduit Opening

Micro QD

Normally Open or Normally Closed

Load

Ground

1

2

3

Note: Load can be switched to pin 2.

Mini QD

Normally Open or Normally Closed

Load

Ground

1

3

2

Note: Load can be switched to pin 3.

Advertising