Rockwell Automation 700-RTC Type RTC Fixed Time Solid-State Timing Relays User Manual
Installation instructions, Description, Ul listed
 
1
Publication 700-IN004C-EN-P - October 2009
Installation Instructions
Bulletin 700 Type RTC Fixed Time Solid-State 
Timing Relays
Instruction Sheet
Important: Save these instructions for future reference.
Description
Bulletin 700 Type RTC Fixed Time timing relays are designed for applications 
where a specific time delay is required and inadvertent timing changes must be 
avoided. They offer the reliability and accuracy of solid-state timing along with 
the contact isolation of conventional electromechanical relays. The contacts 
are hermetically sealed in glass for reliability.
The time delay is factory set at the value stated on the nameplate. The 
operating mode is either On-Delay or Off-Delay, not convertible. Relays are 
supplied with up to two timed contacts and two instantaneous contacts.
The Normally Open (N.O.) and Normally Closed (N.C.) contacts are designed 
to be changed or added in the field. A relay can be easily modified to have any 
combination of N.O. and N.C. contacts, limited to two timed and two 
instantaneous contacts maximum.
Note
: If (2) Normally Closed (N.C.) contact cartridges are required for the
instantaneous positions of C5/C6 and C7/C8, they must NOT be field 
installed. Please order this contact configuration direct from the factory.
UL Listed
Bulletin 700 Type RTC relays are listed by Underwriters’ Laboratories, Inc. for 
use in Class I, Division 2, Groups A, B, C, and D hazardous locations as 
defined by the National Electric Code.