Actuator Consideration

Limit switches are designed for proper performance with

the actuators with which they are supplied.

Supplementary actuators should not be used unless the

limit switches are specifically designed for them.

Wrong

Wrong

Free Position

Interference

Wrong

Wrong

Right

Right

End of

Overtravel

Wrong

End of

Overtravel

Operated

Position

Free Position

Operating mechanism for limit switches should be so

designed that under any operating or emergency

conditions the limit switch is not operated beyond its

overtravel limit position. A limit switch should not be used

as a mechanical stop.

For limit switches with lever actuators, the actuating force

should be applied as nearly perpendicular to the lever as

practical and perpendicular to the shaft axis about which

the lever rotates.

NonĆOverriding

Right

NonĆOverriding

Wrong

Right

Where relatively fast motions are involved

cam arrangements should be such that

the actuator does not receive a severe

impact. Cams should be designed such

that the limit switch will be held operated

long enough to operate relays, valves, etc.

Cam or dog arrangements should be such

that the actuator is not suddenly released

to snap back freely.

A limit switch actuator must be allowed to

move far enough for positive operation of

the contacts.

For limit switches with pushrod actuators

the actuating force should be applied as

nearly as possible in line with the pushrod

axis.

Wrong

Overriding Cam

Right

Overriding Cam

Wrong

Right

Wrong

Right

Cam

Actuator

Free Position

Right

Operating

Position

Wrong

Right

Wrong

Cam

Operating

Position

Operated

Position

Location and Installation

Cam

Wrong

Right

Limit switches should be mounted rigidly and in

readily accessible locations with suitable

clearances to permit easy service and replacement

when necessary. Cover plates should face the

maintenance access point.

Limit switches should not be used in locations

where temperature or atmosphere conditions are

beyond those for which they have been specifically

designed.

Limit switches should be placed in locations where

machining chips do not accumulate under normal

operating condictions.

NonĆoverriding

Cam

Wrong

Right

NonĆoverriding

Cam

Wrong

Right

Wrong

Right

Limit switches should not be submerged in or

splashed with oils, coolants or other liquids.

Wrong

Right

The location of oiltight limit switches and the method of

connecting them should be such that condensation in the

conduit cannot enter the switch enclosure.

Wrong

Right

NonĆoverriding

Cam

Limit switches should be mounted in locations

which will prevent false operation by normal

movements of operator or machine components.