Assembly of Reversing Starters

2

1

3

Assemble the reversing starter:

• Place the mechanical interlock

between contactors

• Insert the dovetail connector

from rear side

• Attach the parallel connection

on line side

• Attach the reversing connection

and the overload relay on load side

Snap the starter combination onto the metal hat rail in the enclosure base.

Snap the 800F contact blocks onto the device support:

• Pos. 1 (left):

N.O. contact

• Pos. 2 (center): N.C. contact

• Pos. 3 (left):

N.O. contact

Do the control wiring according the wiring diagram / wiring table.

Mount the 800F push button operators into the cover.