Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start User Manual

Page 35

Advertising
background image

Rockwell Automation Publication 520-QS001A-EN-E - March 2014

35

PowerFlex 520-Series Adjustable Frequency AC Drive

Drive and Adapter Status Indicators

Setting the IP Address, Subnet Mask, and Gateway Address

Setting an IP Addresss Using Parameters

1. Verify that parameter C128 [EN Addr Sel] is set to 1 “Parameters”.

This parameter must be set to “Parameters” to configure the IP address
using parameters.

2. Set the value of parameters C129 [EN IP Addr Cfg 1] through

C132 [EN IP Addr Cfg 4] to a unique IP address.

3. Reset the adapter by power cycling the drive.

Setting a Subnet Mask Using Parameters

1. Verify that parameter C128 [EN Addr Sel] is set to 1 “Parameters”.

This parameter must be set to “Parameters” to configure the subnet mask
using parameters.

2. Set the value of parameters C133 [EN Subnet Cfg 1] through

C136 [EN Subnet Cfg 4] to the desired value for the subnet mask.

3. Reset the adapter by power cycling the drive.

Setting a Gateway Addresss Using Parameters

1. Verify that parameter C128 [EN Addr Sel] is set to 1 “Parameters”.

This parameter must be set to “Parameters” to configure the gateway
address using parameters.

2. Set the value of parameters C137 [EN Gateway Cfg 1] through

C140 [EN Gateway Cfg 4] to desired value for the gateway address.

3. Reset the adapter by power cycling the drive.

Esc

Sel

FWD

ENET LINK

EtherNet/IP

ENET LINK

EtherNet/IP

Item

Name

State

Description

ENET

Off

Adapter is not connected to the network

Steady

Adapter is connected to the network and drive is controlled through Ethernet.

Flashing

Adapter is connected to the network but drive is not controlled through Ethernet.

LINK

Off

Adapter is not connected to the network.

Steady

Adapter is connected to the network but not transmittingdata.

Flashing

Adapter is connected to the network and transmitted data.

FAULT

Flashing Red

Indicates drive is faulted.

Default = 0.0.0.0

192.168.1.62

[EN IP Addr Cfg 1]

[EN IP Addr Cfg 2]

[EN IP Addr Cfg 3]

[EN IP Addr Cfg 4]

Default = 0.0.0.0

255.255.255.0

[EN Subnet Cfg 1]

[EN Subnet Cfg 2]

[EN Subnet Cfg 3]

[EN Subnet Cfg 4]

Default = 0.0.0.0

192.168.1.1

[EN Gateway Cfg 1]

[EN Gateway Cfg 2]

[EN Gateway Cfg 3]

[EN Gateway Cfg 4]

Advertising