Rockwell Automation 25-COMM-E2P PowerFlex 520-Series Communication Adapters User Manual

Page 2

Advertising
background image

PowerFlex 520-Series Communication Adapters

Publication 520COM-IN001C-EN-P - July 2014

Supersedes Publication 520COM-IN001B-EN-P - September 2013

Copyright © 2014 Rockwell Automation, Inc. All rights reserved.

Allen-Bradley, Rockwell Software, Rockwell Automation, PowerFlex, and TechConnect are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

U.S. Allen-Bradley Drives Technical Support - Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, E-mail: [email protected]
Online:

www.ab.com/support/abdrives

5
4
3
2
1

Red
White
Bare
Blue
Black

4

5

Terminal

Color

Signal

Function

5

Red

V+

Power Supply

4

White

CAN_H

Signal High

3

Bare

SHIELD

Shield

2

Blue

CAN_L

Signal Low

1

Black

V-

Common

Maximum Wire Size

Minimum Wire Size

Torque

3.33 mm

2

(12 AWG)

0.08 mm

2

(28 AWG)

0.44...0.54 Nm (3.9...4.8 lb-in)

Wiring the DeviceNet Adapter

How to Remove the Control Module Back Cover if Required

25-COMM-D
25-COMM-P
25-COMM-E2P

Install the Communication Adapter

DeviceNet adapter with optional 25-ENC-1
Incremental Encoder Input shown

Communication adapter label
(pre-attached)

Space for optional Incremental
Encoder Input label

Note: Incremental Encoder Input is for PowerFlex 525 only.
You can install both the communication adapter and optional
Incremental Encoder Input on the same Control Module Back Cover.

Advertising