Installation and Operating Instructions

Bulletin 440P DIN 50041 IEC/Large Metal Body Safety Limit Switch

IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE.

Specifications

See the Sensors catalog for additional information and product
selection.

Installation of Allen-Bradley/ Guardmaster
products should be in accordance with local and/
or national codes. Servicing energized industrial
control equipment can be hazardous if not in
accordance to recommended safety procedures.

AC/DC Designation A600; Q600

AC/DC Utilization Category

Alternating current: AC15 (50/60 Hz)
Ue (V): 120 240 500 600
le (A): 6 3 1.4 1.2
Direct current: DC13
Ue (V): 125 250 500 600
le (A): 0.55 0.27 0.13 0.1

Max. Fusing Rate 10 A fast acting

Impulse Voltage (Uimp) 2500V

Enclosure Protection IP66

Pollution Degree 3

Storage/Operating

Temperature

-25…+65 °C (-13…+149 °F)

Direct Opening Action Normally closed only (safety circuit)

Conductor Sizes Use copper conductors only

Stranded [mm

2

(in.

2

)]

0.75…2.5 (0.02…0.09)
(18…14 AWG)

Solid [mm

2

(in.

2

)]

0.75…2.5 (0.02…0.09)
(18…16 AWG)

Operator heads with adjustable or flexible
actuators are NOT intended for safety
applications.

IMPORTANT

ATTENTION

Torque/Mounting

Rotating Operator Heads

When rotating operator heads, follow these steps:

1. Loosen the head mounting screws and remove the operating

head from the switch enclosure.

2. Orient the operator head in one of the four positions offered.

Make sure the loose parts are positioned correctly before
affixing the operator head to the switch enclosure.

3. Tighten the four screws per the recommended torque

specifications above.

Location

Torque

Heads

1.2 N•m (0.86 lb•ft)

Covers

1.6 N•m (1.18 lb•ft)

M5 Mounting

2.5…3.0 N•m (1.84…3.21 lb•ft)

Wire Clamp

0.9…1.0 N•m (0.66…0.74 lb•ft)

Lever

Clamp

M5 Hex Screw

1.8 N•m (1.33 lb•ft)

M3/M4 Hex Screw

1.5 N•m (1.11 lb•ft)

Adj. Lever Screw

1.0 N•m (0.74 lb•ft)

Conduit

1.0 N•m (0.74 lb•ft)

Internal operator head components can become
dislodged when removing operator heads. Use
caution during removal and assembly.

Check for switch operation with a continuity
indicator before placing product in service.

IMPORTANT