Control terminals, Grounding, Devicenet terminals – Rockwell Automation 592-ECxxx E3 and E3 Plus Solid State Overload Relay User Manual

Page 2: Wiring diagrams, Table 1 - control terminal designation, Table 2 - devicenet terminal designation

Advertising
background image

Control Terminals

The following table defines the E3 Overload Relay control terminal
designations.

Features are available only with the E3 Plus Overload Relay (cat. nos. 193/592-EC2 and

193/592-EC3).

Available only on cat. nos. 193/592-EC5_ _.

An earth ground connection to this terminal will assist in obtaining compliance with

electromagnetic compatibility requirements.

The use of shielded cable is recommended for the positive PTC thermistor circuit to assist

in obtaining compliance with electromagnetic compatibility requirements.

Available only on cat. nos. 193/592-EC3_ _ and 193/592-EC4_ _.

DeviceNet Terminals

The following table defines the DeviceNet connector terminal
designations.

Table 1 - Control Terminal Designation

Terminal
Designation

Reference

Description

1

IN 1

General-purpose sinking input number 1

2

IN 2

General-purpose sinking input number 2

3

IN 3

General-purpose sinking input number 3



4

IN 4

General-purpose sinking input number 4



5

V+

+24V DC supply for inputs

6

V+

7

IN 5

General-purpose sinking input number 5

8

IN 6

General-purpose sinking input number 6

End Earth

Ground

13/14

OUT A

Output A

23/24 OUT

B

Output

B



95/96

Trip Relay

Trip Relay

1T1/1T2

PTC

Thermistor (PTC) input



S1/S2

--

External ground fault sensor input



Table 2 - DeviceNet Terminal Designation

Terminal Signal

Function

Color

Black

Common

V-

1

Blue

Signal Low

Signal High

CAN_L

2

Non-insulated

Shield

Drain

3

White

CAN_H

4

Red

Power Supply

V+

5

Grounding

The following grounding recommendations are provided to ensure electromagnetic compatibility compliance during installation:

·

The earth ground terminal of the E3 Overload Relay shall be connected to a solid earth ground via a low-impedance connection.

·

Installations employing an external ground fault sensor shall ground the cable shield at the sensor with no connection made at the E3 Plus
Overload Relay.

·

The PTC thermistor cable shield shall be grounded at the E3 Plus Overload Relay with no connection made at the opposite end.

Wiring Diagrams

WARNING: When working on energized circuits, do not rely on the voltage and current information provided by the E3 and E3 Plus for personal safety. Always
use a portable voltage or current measurement device and measure the signal locally.

Bulletin 193 / 592 E3 and E3 Plus Solid State Overload Relay

2

Publication 193-IN055B-EN-P - August 2013 PN-154492 DIR 10000279804 (Version 01)

Figure 2 - Three-Phase D.O.L &
Single-Phase Wiring Diagrams

E3/E3 Plus

E3/E3 Plus

L1

L2

L1

L3

L2

2/T1

6/T3

M

M

S.C.P.D.

Single-Phase Full-Voltage

Three-Phase Direct-On-Line

T2

T2

T3

T1

T1

L2

L3

L1

Voltage Input Module

(For 193/592-EC5 only)

L2

L1

Voltage Input Module

(For 193/592-EC5 only)

4/T2

2/T1

6/T3

4/T2