Rockwell Automation 160 160 Ser C Custom Firmware P04, FRN 7.06, A005 User Manual
160 series c custom firmware, Instructions
 
Instructions
160 Series C Custom Firmware
P04 Option - FRN 7.06 A005
Introduction
The P04 option differs from the standard version 7.06 firmware with the 
following function changes:
•
2-Step MOP Reference - page 1
•
4-Step Preset Reference - page 2
•
Direction Change Ramp - page 2
A summary of parameter differences is listed on page 3.
Firmware Changes
2-Step MOP Reference
The standard drive “Two-Wire Accel/Decel Control” input mode 
(parameter 46 - setting 4) has been modified. Terminal functions have been 
re-defined as shown. 
A maintained Run Forward or Run Reverse input will provide both a 
direction and a start command to the drive and maintain the active speed 
reference. An Accel input while the drive is running will increase the speed 
reference. Opening the Run Forward or Run Reverse will decrease the 
speed reference to the minimum frequency parameter setting (P32) and 
command the drive to stop. Momentarily opening Run Forward or Run 
Reverse will cause the drive to operate at a lower speed reference.
!
ATTENTION:
This Custom Firmware has been designed for a
specific application and differs from the standard bulletin 160 
product offering. It must be installed and run only under this 
custom application. Attempting to run this Custom Firmware 
under any other type of application or condition could result in 
unpredictable and/or hazardous conditions.
Accel
56
7
8
Common
Run Reverse
Run Forward
TB3
TB3-8 Open
Maintain Speed Reference
TB3-8 Closed
Increase Speed Reference