Rockwell Automation 1336S_F_E_T_R Transistor and Thyristor (SCR) Service User Manual
Service instructions
 
Service Instructions
Description
These instructions cover the proper method of replacing transistor and 
SCR modules in the 1336 family of drives. Failure to properly prepare 
the mounting surface or to torque the components to rated specifications 
will result in decreased service life of the replacement components.
Contents
Description
Page
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Surface Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Thermal Grease Requirements . . . . . . . . . . . . . . . . . . . . . . . . . 3
Torque Mounting Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Torque Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Safety Precautions
!
ATTENTION: Some printed circuit boards and drive 
components may contain hazardous voltage levels. 
Remove and lock out power before you disconnect or 
reconnect wires, and before you remove or replace fuses 
and circuit boards. Verify bus voltage by measuring the 
voltage between +DC and - DC on Terminal Block TB1. 
Do Not attempt to service the drive until the bus voltage 
has discharged to zero volts.
!
ATTENTION: Potentially fatal voltages may result from 
improper useage of oscilloscope and other test equipment. 
The oscilliscope chassis may be at a potentially fatal 
voltage if not properly grounded. If an oscilliscope is used 
to measure high voltage waveforms, use only a dual 
channel oscilliscope in the differential mode with X100 
probes. It is recommended that the oscilliscope be used in 
the A minus B Quasi-differential mode with the 
oscilliscope chassis correctly grounded to an earth ground.
Transistor and Thyristor (SCR)
Replacement for 1336 PLUS, PLUS II, 
FORCE, IMPACT and REGEN Drives.