Rockwell Automation 1502 Electrically-Held to Mechanically Latched Contactor - Retrofit Instructions User Manual
Page 7

Electrically Held to Mechanical Latch Contactor • Retrofit Instructions
3
1502-IN001%-EN-P – -XQH
2. Using two 7/16” wrenches, loosen the auxiliary contact assembly-
retaining bolt and slide the electrically held auxiliary contact
assembly out of the front of the contactor.
3. Disconnect the coil leads from the auxiliary contact assembly
using a Phillips Screwdriver.
Figure 3 – Disconnecting Coil Leads from Auxiliary Contact Assembly
Install the Latch Mechanism
1. Place the contactor on to its back to expose the underside of the
contactor base.
2. Install the rubber stop as shown in the drawing below:
Rubber Stop
(Install rubber stop as shown
with supplied components.)
Rubber Stop
(Install rubber stop as shown
with supplied components.)
Figure 4 – Installing Latch Mechanism Rubber Stop
3. Separate the latch mechanism from the latch clamp plate by
removing the 3 bolts which hold them together with a ½” wrench.
4. Slide the latch mechanism into the front of the contactor in the
space right of the closing coils. Pull the trip coil leads out of the
back of the contactor.