Chapter 3

Control Description

3-2

Table 3.A

Configuration Parameters

Port A

Port B

Name

Function

400

300

Digital Input

Fast Source, Discrete Input to Drive

401

301

Analog In 1

Fast Source, Analog 1 Input to Drive

402

302

Analog In 2

Fast Source, Analog 2 Input to Drive

403

303

Analog In 3

Fast Source, Analog 3 input to Drive

404

304

Analog In 4

Fast Source, Analog 4 Input to Drive

450

350

Digital Output

Fast Sink, Discrete Output from Drive

451

351

Analog Out 1

Fast Sink, Analog 1 Output from Drive

452

352

Analog Out 2

Fast Sink, Analog 2 Output from Drive

453

353

Analog Out 3

Fast Sink, Analog 3 Output from Drive

454

354

Analog Out 4

Fast Sink, Analog 4 Output from Drive

Table 3.B

SetĆUp Parameters

Program Terminal Units

Internal Units

Port A

Port B

Description

Default

Range

Default

Range

550

500

ADC Scale 1

1

(-16, 16)

2048

±

32767

551

501

ADC Offset 1

0

(-20, 20)

0

±

4096

552

502

ADC Scale 2

1

(-16, 16)

2048

±

32767

553

503

ADC Offset 2

0

(-20, 20)

0

±

4096

554

504

ADC Scale 3

1

(-16, 16)

2048

±

32767

555

505

ADC Offset 3

0

(-20, 20)

0

±

4096

556

506

ADC Scale 4

1

(-16, 16)

2048

±

32767

557

507

ADC Offset 4

0

(-20, 20)

0

±

4096

558

508

Digital Out 1

10 at Zero Spd

(0,15)

10

0 - 15

559

509

Digital Out 2

5 Drive Running

(0,15)

5

0 - 15

560 - 574

510 - 524

Not Used

575

525

DAC Scale 1

1

(-1,1)

32767

±

32767

576

526

DAC Offset 1

0

(-20, 20)

0

±

4096

577

527

DAC Scale 2

1

(-1, 1)

32767

±

32767

578

528

DAC Offset 2

0

(-20, 20)

0

±

4096

579

529

DAC Scale 3

1

(-1, 1)

32767

±

32767

580

530

DAC Offset 3

0

(-20, 20)

0

±

4096

581

531

DAC Scale 4

1

(-1, 1)

32767

±

32767

582

532

DAC Offset 4

0

(-20, 20)

0

±

4096

583 (1)

533 (1)

Digital In 1

11 Stop

(0,15)

11

0 - 15

584

534

Digital In 2

9 Jog 2

(0,15)

9

0 - 15

585

535

Digital In 3

12 Start

(0,15)

12

0 - 15

586

536

Digital In 4

14 Drv Flts

(0,15)

14

0 - 15

587 - 598

537 - 548

Not Used

599

549

Adapter Board Identifier

3.xx

-

(1) Digital In 1 is designed for use with a Normally Closed (NC) operator device. Applying positive control voltage to Digital In 1