port is less than 5% of the full range. It is not recommended that the span
calibration be performed in the field unless a high quality calibrator is available.
Optional switch settings. Default is
Normal (switch set to off).
Power in, 24Vac/dc
Common is shared with
output
Output, Current or
Voltage.
Common is shared with
power supply
NOTE: The range and options switch can be
changed while the unit is powered. However,
the output jumpers can only be changed while
the unit is unpowered.
DO NOT CONNECT POWER TO
THE ‘OUT’ TERMINAL AS THE
UNIT WILL BE DAMAGED!
+ 24 V AC/DC -
ANL IN 0 +
ANL IN 0 -
Analog Current/
Voltage Input
ANL COM
Loop power supply
ZERO
COM
ZERO
OUT
PWR
Remote zero switch
(optional)