Electrical connections – Rockwell Automation 1502 Medium Voltage 400A Contactor - Series E User Manual

Page 18

Advertising
background image

18

Rockwell Automation Publication 1502-UM052H-EN-P - June 2013

Chapter 3

Installation

Figure 8 - Mechanical Latch Dimensions (Optional)

Electrical Connections

A wire harness connects the control wiring to the contactor from the low voltage
control panel. The harness connects to a wire plug on the lower left side of the
contactor. If the contactor is supplied as an OEM component for installation in a
custom application, the following two control options and a connecting wire
harness are available from Rockwell Automation.

• IntelliVAC and IntelliVAC Plus control modules
• Electromechanical control panel (for latch contactors only)

Connect incoming power to the line side terminals at the top, rear of the
contactor near the control fuse clips. Use 3/8 in. (10 mm) bolts torqued to
20 lb

•

ft (292 N

•

m) to secure the connection.

Connect outgoing power to the load side terminals halfway down the rear of the
contactor. Use 3/8 in. (10 mm) bolts torqued to 20 lb

•

ft (292 N

•

m) to secure the

connection.

For mechanically latched contactors, ensure the manual trip button in the cabinet
door is in line with the trip lever on the contactor.

2 . 9 3

1 . 5 3

Advertising