Output screen – Rockwell Automation 931U-C9A2C-OP Active Converter, Universal User Manual
Page 12

12
Fields
Description
10V Attenuator
This check box allows you to set ‘Input High’ and ‘Input Low’ values in the
software in volts up to 10 V.
Note: The 931U-C9A2C-OP will only accept values up to 10 V if the attenu-
ator switch on the main board is set to the 10 V setting. If you change the
switches you must recalibrate the voltage input.
Burnout
Sets the action in case of sensor burn-out or disconnection. Upscale sends
the output to 22 mA, downscale sends the output to 3.7 mA.
Type
Allows you to choose between thermocouple or RTD types. Not shown for
other input types. Note: you can set up your own linearisation tables here by
choosing ‘user defined’.
Input connection
Is the input connected in two, three or four wire mode. For RTD and resist-
ance inputs only. Sets up the lead length compensation.
Output screen
Fields
Description
Range
Sets the output range, normally 4.00 mA to 20.00 mA.
Transfer function
X
1
gives the usual proportional output.
Output action
Set to direct or reversed. Direct gives the usual proportional output. For
reversed action, the input low value gives a 20 mA output and the high value
a 4 mA output.