Wiring – Rockwell Automation 1336S NEMA 4/12 Enclosure Kit User Manual

Page 2

Advertising
background image

2

1336 PLUS and PLUS II IP 65/54 (NEMA Type 4/12) Enclosure Kit

To install the drive, follow these steps:

1. Place the gasket, with the gasket paper still intact, around the

cutout area on the inside of the enclosure. Assure that the
mounting holes are aligned properly (mounting holes are not
equally spaced).

2. Peel away the gasket paper.

3. Firmly press the gasket in place aligning with the enclosure holes.

4. Remove the screws holding the drive mounting rails to the drive

back panel.

5. Install the drive in the enclosure using the mounting screws

provided with the kit.

6. Torque all mounting screws to 2.9 N-m (26 lb.-in.).

7. Connect the fan wires (A4 Frames & Up) as shown in the next

section.

Wiring

The following diagram shows the typical wiring diagram for all
frames. Note that a fan is not required on A1-A3 frames.

!

ATTENTION: Electric shock can cause injury or death.
Disconnect all power before working on this product.

!

ATTENTION: Drive heatsink surface temperature may be
at or near 100 degrees C (212 degrees F). To avoid burns,
do not make contact with the drive heatsink.

Typical Inside View

Typical Wire Connections
(460V Connections Shown)

Fan

Typical Transformer/Fan Location

Pre-assembled Wires (Furnished)

Typical Drive Location

0V

380V

415V

115V

0V

460V

Fan

T1

19

TB3

TB2

TB1

20 21 22 23 24 25 26 27 28 29 30

TETE 1

1

2

2

3 4 5 6 7

P
E

P
E

D

C

+

D

C

J

2

R S T U V W

TB1

P
E

P
E

D
C

+

D
C

R S T U V W

8 9 10 11 12 13 14 15 16 17 18 A1 A2

Advertising