Rockwell Automation 1414-CCZxxxxxxx Current Sensor User Manual

Current sensor, Installation instructions, About the current sensor

Advertising
background image

Installation Instructions

Current Sensor

Catalog Numbers 1414-CCZ10FZWZDC, 1414-CCZ10FZWZDD,
1414-CCZ10FZWZDE, 1414-CCZ10FZWZDA

About the Current Sensor

These AC current sensors can be used to monitor fans, pumps, motor operation and failure,
conveyor belt, bearing loss, and other electrical loads. The current sensor requires no external
power supply since internal electronics are powered by the AC line induction being monitored
with an output-limited voltage clamp <12V DC.

Topic

Page

About the Current Sensor

1

Important User Information

2

Install the Current Sensor

3

Specifications

4

ATTENTION: Never open a current-transformer secondary circuit with primary
current applied. Wiring between the CTs and the power monitor should include a
shorting terminal block in the CT secondary circuit. Shorting the secondary with
primary current present allows other connections to be removed if needed. An open
CT secondary with primary current applied produces a hazardous voltage, which
can lead to personal injury, death, property damage, or economic loss.