IV. Conversion Module Wiring Diagram

The following diagrams show the connections from the existing B821-108 swing-arm, through the conversion module, 1492
cable and to the 1756-IB16 or 1756-IC16 input module. The diagrams can be used as an aid in possible system trouble-
shooting.

1756-IB16

1492-CABLE003X

1492-CM800-LD007

Conversion: B821-108 to 1756-IB16 with 1492-CM800-LD007

B821-108 Swing Arm

3

1

1

19

2

3

7

4

8

5

11

6

12

7

17

8

18

9
10
11

4

12

10

13

14
20

15

5

16

6

17

15
16

18

20

14

2

3

+

-

Input 5

Input 7

Input 6

Input 8

Input 1

Input 3

Input 2

Input 4

Group 1 Common

Not Used
Not Used

10

GND-0

IN-0

1

IN-1

2

IN-2

3

IN-3

4

IN-4

5

IN-5

6

IN-6

7

IN-7

8

IN-8

11

IN-9

12

IN-10

13

IN-11

14

IN-12

15

IN-13

16

IN-14

17

IN-15

18

Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green

GND-1

20

9

GND-0

19

GND-1

9

Group 2 Common

13

Group 3 Common

19

Group 4 Common

Group 1 Supply Volt
Group 2 Supply Volt
Group 3 Supply Volt
Group 4 Supply Volt

Not Used
Not Used

Conversion Module Installation and Application Considerations

The voltage range of the B821-108 module is 10-60V DC and the 1756-IB16 is 10-30V DC. If the input source voltage is

greater than 30V DC, use the 1756-IC16.

The input delay times for the B821-108 module versus 1756-IB16 module are as follows:

B821-108

1756-IB16

a) Off-to-On Delay

2.5ms (min),11ms (max)

1ms (plus selectable filter)

b) On-to-Off Delay

2.5ms (min),11ms (max)

2ms (plus selectable filter)

The B821-108 has 4 groups (allowing 4 separate power supplies) and the 1756-IB16 has 2 groups. This module/cable

combination ties Groups 1 & 2 from the B821-108 to Group 0 on the 1756-IB16 and it ties Groups 3 & 4 from the B821-108 to
Group 1 on the 1756-IB16. Field wiring modification must be made to accommodate this if multiple supplies were used. If 4
supplies were used, 2 must be removed. NOTE: To allow for multiple supplies in this conversion, the Inputs do not map directly
to the equivalent input. For example: Input 5 on the B821-108 maps to Input 8 on the 1756-IB16, the user needs to account for
this in the controller program.

Refer to your B821-108 and 1756-IB16 Installation Manual wiring schematics and diagrams for more details.

[Reference Doc: 41170-756 (Version 03)]

There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and output module). Read and understand these
considerations before installation.