Pneumatic connections – Rockwell Automation 1414-IPZxxxxx_CPZxxxxx_CPDxxxxx Differential Air Pressure Transmitter User Manual
Page 5
 
Differential Air-pressure Transmitter 5
Publication 1414-IN011B-EN-P - July 2010
The analog output signal is available on the OUT terminal. This signal is jumper selectable for 
either a voltage output or a standard loop-powered 4…20 mA output signal type. When voltage 
mode is selected, either 0…5V DC or 0…10V DC can also be selected. These options are 
indicated on the device circuit board. The analog output signal is typically connected directly to 
the Building Automation System (B.A.S.) and used as a control parameter or for logging 
purposes.
For voltage type output signal the device has a minimum load that it is able to drive, similarly for 
current type output signal the device has a maximum load that it is able to drive with a particular 
power supply voltage. Observe and follow these ratings in the Specification section or inaccurate 
reading may result.
The 4…20 mA output signal can easily be converted to a 1…5V DC signal for controllers 
accepting this type of input. Simply insert a 250 
Ω (0.1% is best) resistor between the ‘+’ and ‘-’
inputs of the controller. This will convert the 4…20 mA signal to the desired 1…5V DC.
Pneumatic Connections
The two pressure ports on the end of the enclosure are labeled High and Low. The output signal 
reads a positive value when the port pressure is higher on the High port than the Low port so 
ensure these ports are connected correctly.
Use 0.170 in. I.D. flexible tubing for the High and Low pressure connections. Arrange the tubing 
to minimize stress on the connections and ensure there are no kinks in the tubing. For most 
accurate measurements, do not leave the Low port open to the atmosphere, run a return line 
from the Low port to the vicinity of the point being measured.
Ensure the tubing to be used is clean and do not allow material to fall into the pressure ports as 
contamination could damage the sensor.
When removing tubing use care to avoid breaking the ports. In some cases it is better to cut the 
tubing off rather than pulling it off but be careful not to cut the fitting or an air leak may occur.
Differential Air-pressure Transmitter Configuration
The transmitter is configured with push-on type jumpers on the circuit board as shown on the
drawing. These jumpers are used to select the output signal type and the input
pressure range.
The module is factory configured to operate in the 4…20 mA output mode. You can change the 
voltage mode by moving the three jumpers from the positions marked Current to the positions 
marked Voltage. Before moving these jumpers, study the current jumper position and then move 
the jumpers to the new position. If these jumpers are rotated 90 degrees and installed incorrectly 
the product will not work and device damage may occur. 
Once the output mode is changed to voltage, the output scale may be changed to either 
0…5V DC or 0…10V DC. This is done by moving the single jumper to the 0…5V or 0…10V 
position.