Rockwell Automation 1426-MxE-xxx PowerMonitor 5000 Unit Firmware Revision Update Installation Instructions User Manual

Page 8

Advertising
background image

8

Rockwell Automation Publication 1426-IN004A-EN-P - December 2013

PowerMonitor 5000 Unit Firmware Revision Update

14. In the WinZip Caution dialog box, click Yes.

The ControlFLASH™ utility opens.

Directions on updating the firmware revision are found in the

Update the

Device Firmware Revision with the ControlFLASH Utility

section.

Update the Device Firmware
Revision with the
ControlFLASH Utility

When updating the firmware revision, refer to the

Access Product Firmware

Revision

section for

instructions on obtaining the latest firmware revision from

the Rockwell Automation download center.

1. Check Yes, I want to launch ControlFLASH and click Close.

IMPORTANT

The ControlFLASH utility does not update the firmware if any Class 1
connections (generic or electronic data sheet (EDS) Add-on Profile
connections) exist. A connection exists if the Network Status indicator is either
solid green (connection active) or blinking red (connection timed out). Use the
Studio 5000 Logix Designer™ application to connect to the controller that owns
each connection and inhibit the connection. After successfully updating the
power monitor firmware, you can uninhibit the connections. Note that you can
edit connection properties to reflect the new power monitor firmware revision.

Advertising