Temperature, Pollution, Specifications (cont.) – Rockwell Automation 1503FC IntelliVAC Contactor Control Module - Series E User Manual
Page 11

Product Description
1-7
1503-UM053B-EN-P – June 2013
Table 1.B – Mechanical Ratings
Temperature
Operating: 0° to 60°C ambient at the control module
Non-Operating: -40° to 85°C
Altitude
-1000 to 5000 meters
Pollution
Pollution level II (as defined by UL 840 and IEC 60664-1)
Humidity
95% non-condensing
Shock and Vibration
(Operational)
Shock – 15 g peak, 11 milliseconds
Vibration – 10 to 57 Hz, 0.015 inch displacement peak to peak
– 57 to 150 Hz, 2.5 g acceleration
Ambient temperature is derated at altitudes above 1,000 meters (3,300 feet).
Please refer to Table 1.C.
Table 1.C – Altitude Derating
Altitude
Maximum Operating Ambient
at the control module (°C)
-1000 to 0
60
1 to 1000
60
1001 to 2000
58
2001 to 3000
56
3001 to 4000
54
4001 to 5000
52
Derate by 2°C / 1000 m for high altitude operation
5.1 (0.20)
Dimensions in mm (inches)
29.7
(1.17)
174.8
(6.88)
185.3
(7.29)
59.4
(2.34)
165.9 (6.53)
5.8 (0.228)
2 places
5.1 (0.20)
Dimensions in mm (inches)
29.7
(1.17)
174.8
(6.88)
185.3
(7.29)
59.4
(2.34)
165.9 (6.53)
5.8 (0.228)
2 places
Figure 1.3 – Mechanical Dimensions