Rockwell Automation 1494C-JK1_JK2 Cable Operated Disconnect Pin Replacement Kit User Manual
Cable operated disconnect pin replacement kit, 6attention

2
Remove handle and mechanism bracket
1
Remove defeater bracket
Install defeater bracket
7
Install handle and mechanism bracket
30 - 40 lb-in
(30A - 200A)
60 - 80 lb-in
(400A - 600A)
3
Remove and discard
retaining ring
4
Remove and
discard old pin
and washer
5
Install new pin
and washer
6
Install new
retaining ring
8
7-11 lb-in
Cable Operated Disconnect Pin Replacement Kit
1494C-JK1 - (30A - 200A):1494C-CM1 thru CM8 / CMX1 thru CMX8
1494C-JK2 - (400A):1494C-CM9 thru CM12 / CMX9 thru CMX12
(600A):1494C-CM13 thru CM16 / CMX13 thru CMX16
WARNING
To prevent electrical shock, disconnect from power source before installing or servicing. Install in suitable enclosure. Keep
free from contaminants.
6
ATTENTION:
CHECK FOR PROPER OPERATION . Upon completion of the
pin replacement, if further adjustments are needed see instruction sheet(s)*
included with the pin replacement kit.
* 30A - 200A use 42052-151-01
* 400A use 42052-159-01
* 600A use 42052-191-01
During pin replacement, make sure both handle and disconnect switch are
either in the “ON” position or “OFF” position for ease of installation.
PN-81093
DIR 10000119196
(Version 00)
Printed in Mexico