Rockwell Automation 1326-xxxx Cable Bulkhead Connector User Manual
Page 11

Publication 1326-IN025B-EN-P - May 2007
Bulkhead Connections for Series B 1326 Cables 11
1. Locate the area of the cabinet wall where you will mount the bulkhead
connector.
2. Mark the places where the four mounting holes and the center
connector opening, a total of five holes, will be located.
3. Drill the four mounting holes and the large center opening.
4. Scrape any paint from the inside surface of the cabinet wall where the
bulkhead flange of the 1326-CPB1-EL-xxx or 1326-CPC1-EL-xxx
cables will make contact.
5. Remove the viton seal from the face of the connector for
1326-CCUx-Ex-xxx, 1326-CPB1x-Ex-xxx, and 1326-CPC1x-Ex-xxx
cables to provide clearance for the cabinet wall.
6. Attach the bulkhead connector through the wall, as shown.
ATTENTION
To avoid a shock hazard, remove power to the motor controller
and motor before installing or removing cables. Failure to do
this can cause personal injury.
The power rail must be mounted with the connectors in an
upright or vertical orientation to the panel. This provides proper
cooling of the modules. Do not mount modules if the power rail
is not within 3° of vertical.
IMPORTANT
A metal-to-metal connection is required for CE compliance.
Maximum width of
cabinet wall
4.623 mm (0.182 in.)