7 - operation, Operation – Rockwell Automation 1336 3-20HP FRN 1.01-3.01 User Manual
Page 71

7
Chapter
7-1
Operation
Start
Jog
Stop
Freq
P
R
Enter
P
R
Control Panel
Programming and Display Panel
Important: 1336 Control Panels are not intended to replace or be
considered a suitable alternative for an operator control station for all
applications. If two-wire control is installed, option L1, L2 or L3 must also
be installed. With two-wire control, the stop pushbutton on all Control
Panels will allow the drive to restart once the button is released. Refer to
codes and standards applicable to your particular system for specific
requirements and additional information.
Drive Restart
Important: The 1336 drive may be programmed to avoid responding to
unintentional start commands. The stop input to the drive must first be
false, then returned to true to restart the drive:
•
When exiting programming at the Programming and Display Panel.
•
After a power-on reset fault has occurred, if Parameter 14 is set to 0.
– F01 power-on reset is displayed when power is first applied to the
drive and when a fault is cleared.
– If Parameter 14 is set to 1 and Option L1, L2 or L3 is installed to
provide two-wire control, cycling a stop input is not required after
reapplying power or clearing a fault.