Standby mode, Charging mode – Rockwell Automation 1606-XLSBUFFER48 Power Supply Reference Manual User Manual
Page 4

All parameters are specified at 24V, 20A, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
4
Rockwell Automation Publication 1606-RM027A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
5. Standby Mode
Input voltage
nom. DC
48V
Voltage range
nom. 48-56Vdc
Input current
typ. 40mA
Power dissipation
typ. 1.9W
Status lamp
always on
Active signal
high ohmic
Ready signal
low ohmic
6. Charging Mode
Charging current
min. 0.3A
Charging
mode
max. 0.5A
Charging
mode
Charging time
min.
22s / 17s
Initial charge
1)
/ Re-charging
2)
max.
32s / 25s
Initial charge
1)
/ Re-charging
2)
Status lamp
flashes 1.25Hz
Active signal
high ohmic
Ready signal
high ohmic
1) Initial charging is the first charge after voltage is applied to the buffer unit.
2) Re-charging is the charging of the internal capacitors after voltage interruptions of less than 2 minutes.
Fig. 6-1 Re-charging time, 48V
Charge
20
0
5
10
30s
Charging Time
40
80
60
100%
15
20
25
max
min