1336 IMPACT Quick Start Guide

1.

Verify that AC line power and control power match the drive rating.

2.

If an L option is installed, verify that the Stop and Enable interlock inputs are present. If this option is not installed, verify
that jumpers are installed at pins 3 and 4 and 17 and 18 on J5 on A Frame drives or J2 on B Frame and up drives. Refer to
Jumper Locations.

3.

If standard I/O is being used, verify that jumpers are wired correctly.

4.

If Analog Option is installed, verify that parameters are properly configured (refer to the User Manual).

5.

Apply AC power and control voltages to the drive. The LCD display should light and display a drive status of “Stopped”
and an output frequency of “+0.00 Hz.” If the drive detects a fault, a statement relating to the fault will be shown on the
display. Record the information, remove power, and correct the fault source before proceeding.

6.

From the Status Display, press the Enter key (or any key). “Choose Mode” will be displayed. Press the Increment (or
Decrement) key until “Startup is displayed. Press Enter.

Important: All questions can be answered Yes or No. Pressing Enter will select the default (“Y” or “N”). Pressing the
Increment (or Decrement) key will change the selection. Press Enter to select. Choosing “Y” allows you to proceed
through the step, and choosing “No” will advance you to the next step. The figure below shows the steps involved.

Important: Please note the following:

The “Startup” mode can be exited at any time by pressing ESCape until the Status Display is shown. If you wish
to re-enter the “Startup” mode, simply select “Reset Sequence” to start from the beginning. Selecting “Continue”
allows you to resume from the point where you left off.

Completing the last action in any step will automatically take you to the next step.

Pressing SELect will activate line 2 of the display. This must be done for all values.

Press the Increment (or Decrement) key to adjust a value (skip if value is correct). Press Enter to store the value
or retain existing value. Pressing Enter again will cause you to move to the next step (parameter)

7.

Cycle power to activate changes. This completes the “Assisted Startup” procedure. Depending on your application, further
parameter programming and/or “Advanced Startup” may be required. Refer to the User Manual for details.

!

ATTENTION:

In all of the following steps, rotation of the motor may occur. To guard against injury,

incorrect rotation, and possible equipment damage, read each step carefully and perform with caution.

Startup

Encoder?

Regen/
Brake?

Phase
Rotation?

Autotune?

Enter Motor
Data?

Done