Contents of box

Assembling the unit

• Option units

• Terminal block, 1
• Terminal labels, 1 sheet

(1) Insert the tools (see drawing below) into

the slots (one at the top and one at the

bottom) and release the hooks.

(2) Grip the sides of the front panel firmly

and pull forward to remove it.

(3) Match up the upper and lower claws

with the connection points and insert the

board.

(4) Attach the terminal block included with

the Option unit to the outer case.

(5) Make sure the watertight packing is in

place, then press the outer casing into

position. Listen for the click.

Standard slot screwdriver
(unit: mm)

0.4

2.0

20 min.

Handle with care. Do not touch the
electronic parts and do not jolt the
unit.

1618402-5B

Make sure the box contains the following items. If anything is missing or damaged, contact your dealer im-
mediately.

CN9

0.4

2.0

Lieferumfang

Stellen Sie sicher, daß der Karton die folgenden Artikel enthält. Wenn Teile fehlen oder beschädigt sind,
wenden Sie sich an Ihren Fachhändler.

• Optionseinheiten

• Klemmenleiste, 1

• Klemmenaufkleber, 1

Montage der Einheit

Vorsichtig behandeln. Keine elek-
tronische Teile berühren, und das
Gerät nicht Stö ßen aussetzen.

(1) Die Werkzeuge (unten gezeigt) in die Schächte

einstecken (einer oben und einer unten), und

die Haken lösen.

(2) Die Seiten der Frontplatte fest greifen, und zum

Entfernen nach vorne ziehen.

(3) Die oberen und unteren Klauen mit angehobe-

nen Anschlußpunkten ansetzen und die Platte

einsetzen.

(4) Verbinden Sie den Klemmenblock der Option

Unit mit dem äußeren Gehäuse.

(5) Sicherstellen, daß die wasserdichte Packung

vorhanden ist, und dann das Außengehäuse in

Position eindrücken. Bis zum hörbaren Klickger-

äusch eindrücken.

Schraubenzieher
(Einheit: mm)

• Einzelheiten zur Bedienung siehe 900-TC16 Anwenderhandbuch.
• Einzelheiten über Kommunikationsspezikationen siehe Bulletin 900

Kommunikation-Anwenderhandbuch.

20 min.

0.4

2.0

Contenu du carton

Assurez-vous que le carton contient les éléments suivants. Si l'un d'entre eux manque ou est endom-
magé, contactez immédiatement votre fournisseur.

• Unités optionnelles

Assemblage de l'unité

• Bornier, 1

• Etiquette des bornes, 1

Manipulez avec soin. Ne touchez
pas les pièces électroniques et ne
secouez pas l'unité.

(1) Introduisez les outils (voyez le dessin ci-des-

sous) dans les fentes (une en haut et une en

bas) et relâchez les crochets.

(2) Empoignez fermement les côtés du panneau ant-

érieur et tirez celui-ci en avant pour le retirer.

(3) Faites correspondre les griffes supérieures et inf-

érieures aux points de jonction et insérez le ta-

bleau.

(4) Fixez le bornier inclus avec l'unité optionnelle au

boîtier extérieur.

(5) Assurez-vous que le sachet d'étanchéité est en

place puis remontez le panneau extérieur jus-

qu'à ce que vous entendiez un déclic.

Tournevis à fente standard (unité: mm)

• Pour des instructions détaillées sur les opérations, veuillez consulter

le manuel d'utilisation.

• Pour de plus amples détails sur les caractéristiques des

communications, 900-TC16 référez-vous au manuel d'utilisation des
communications du Bulletin 900.

20 min.

Model

Function

900-TC16NCOM

900-TC16NEIM

900-TC16NACCOM
900-TC16NACEIM

900-TC16NCOMP3

900-TCNCOMV2

900-TC16P1V2

900-TC16NCOM

900-TC16NEIM

900-TC16NACCOM
900-TC16NACEIM

900-TC16NCOMP3

900-TCNCOMV2

900-TC16P1V2

Communication (RS-485)
Heater burnout alarm, 1 alarm (CT)
Event inputs, 2 inputs
Heater burnout alarm, 1 alarm (CT)
Communication (RS-485)
Event inputs, 2 inputs
Communication (RS-485)
Heater burnout alarms, 2 alarms (CTs)
Communication (RS-485)
Control output 2 (voltage outputs)
Control output 2 (voltage outputs)
Heater burnout alarm, 1 alarm (CT)

Specifications

Connections

Apply the adhesive terminal label of the option unit to the side of the Temperature Controller.
Use separately available CTs: 900-CT1(Hole diameter: 5.8 mm) or 900-CT3(Hole diameter: 12 mm).

• For detailed operating instructions, please refer to
the 900-TC16 User's Manual.
• For details of the communication specifications, refer to
the Bulletin 900 Communications User's manual.

Kommunikationseinheit Schnittstelle: RS-485

Synchronisation: Start-Stopp (asynchron)

Kommunikation:

Halb-Duplex

Kommunikationsrate: 1.2/2.4/4.8/9.6/19.2/38.4 kbps

Ereigniseingang Kontakteingang:

EIN: 1 k max., AUS: 100 k min.

Kontaktloser

Eingang

EIN: Restspannung: 1.5 V max.

AUS: Leckstrom 0.1 mA max.

Alarm Ausbrennen Heizung Max. Heizungsstrom: 50 A AC
(Alarm Kurzschluss
Heizung) max.

Genauigkeit der Eingangsspannungsanzeige:

±5% FS ±1 Stelle max.

Einstellbereich für den Alarm für das Ausbrennen der

Heizung: 0,1 bis 49,9 A, in 0.1 A-Inkrementen

(Einstellbereich für Alarm für Heizungskurzschluss)

Erkennung EIN Zeit (Erkennung AUS Zeit): 190 ms

Hinweis: Die Werte in Klammern beziehen sich auf die

Alarmeinstellung für Heizungskurzschluss.

Regelausgang 2

Spannungsausgang: 12 VDC, 21 mA

(mit

Kurzschlussschutz)

Technische Daten

Connections

Bringen Sie die selbstklebende Klemmenbeschriftung der Option Unit an der Seite des Temperaturreglers an.

Getrennt erhältliche CTs verwenden: 900-CT1(Lochdurchmesser: 5,8 mm) oder 900-CT3(Lochdurchmesser: 12 mm).

Communication Interface: RS-485
Synchronisation: MARCHE/ARRET (asynchrone)
Communication: semi-duplex

Vitesse de communication:1.2/2.4/4.8/9.6/19.2/38.4 Ko/s

Entrée événement

Entrée avec contact

En fonction: 1k max., hors fonction: 100k min.
Entrée sans contact
En fonction: tension résiduelle 1.5V max.
Hors fonction: courant de fuite 0.1mA max.

Alarme de dysfonctionnement Courant maximal de l’élément chauffant : CA 50 A
de l’élément chauffant Précision de l'indication du courant d'entrée : ± 5 % FS ± 1 chiffre max.
(alarme Heater Short)
max.

Plage de réglage de l'alarme de dysfonctionnement

de l’élément chauffant : de 0,1 à 49,9 A, par

incrément de 0,1 A

(Plage de réglage de l'alarme HS)

Temps d'activation de la détection

(temps de désactivation de la détection): 190 ms

Note : Les valeurs entre parenthèses concernent le réglage

de l'alarme Heater Short.

Sortie de contrôle 2

Sortie de tension : 12 Vc.c., 21 mA

(avec une protection de court-circuit)

Caractéristiques techniques

Connexions

Collez l'étiquette adhésive des bornes de l'unité optionnelle sur le côté de la commande de température.
Utilisez séparément les CT disponibles: 900-CT1(Diamètre du trou : 5,8 mm) ou 900-CT3(Diamètre du trou : 12 mm).

Modèle

Fonction

900-TC16NCOM

900-TC16NEIM

900-TC16NACCOM
900-TC16NACEIM

900-TC16NCOMP3

900-TCNCOMV2

900-TC16P1V2

communication (RS-485)
Alarme de dysfonctionnement de l’élément chauffant, 1 alarme (TC)
Entrées événements, 2 entrées
Alarme de dysfonctionnement de l’élément chauffant, 1 alarme (TC)
communication (RS-485)
Entrées événements, 2 entrées
communication (RS-485)
Alarmes de dysfonctionnement de l’élément chauffant, 2 alarmes (TC)
communication (RS-485)
Sortie de contrôle 2 (sorties de tension)
Sortie de contrôle 2 (sorties de tension)
Alarme de dysfonctionnement de l’élément chauffant, 1 alarme (TC)

Communication Interface:

RS-485

Synchronization: Start-stop (asynchronous)

Communication: Half duplex

Communication rate: 1.2/2.4/4.8/9.6/19.2/38.4 kbps

Event input

Contact input

ON: 1k max., OFF: 100k min.

Non-Contact

input

ON: residual voltage 1.5V max.

OFF: leakage current 0.1mA max.

Heater burnout alarm Maximum heater current: 50 A AC
(Heater Short alarm)

Input current indication accuracy: ±5% FS ±1 digit

max.

Heater burnout alarm setting range: 0.1 to 49.9 A,

in 0.1 A increments

(Heater Short alarm setting range

Detection ON time (detection OFF time) : 190 ms

Note: Values in parentheses apply to the Heater Short

alarm setting.

Control output 2

Voltage output: 12 VDC, 21 mA

(with short-circuit protection circuit)

CT1

900-TC16P1V2
Control Output 2/
CT

12

11

15

14

13

900-TC16NCOMV2
Communications/
Control Output 2

B

A

RS-485

12

11

15

14

13

900-TC16NCOMP3
Communications/
CT2

CT2

CT1

13

14

15

11

12

B

A

RS-485

900-TC16NACCOM
Communication

DO NOT
USE

DO NOT
USE

DO NOT
USE

DO NOT
USE

DO NOT
USE

B

A

RS-485

12

11

15

14

13

900-TC16NACEIM
Event input

EV1

EV2

12

11

15

14

13

900-TC16NEIM
Event input /
CT

CT1

13

14

15

11

12

EV2

EV1

900-TC16NCOM
Communication /
CT

CT1

13

14

15

11

12

B

A

RS-485

DO
NOT
USE

DO
NOT
USE

DO
NOT
USE

Control Output 2

Control Output 2

Control
output 2

·

Voltage

outputs
DC12V
21mA

+

-

+

-

Allen-Bradley Company, LLC
Industrial Components Business
1201 South Second Street
Milwaukee, WI 53204-2496 USA
Phone 440.646.5800

Rockwell Automation
CH-5001 Aarau, Switzerland
FAX ++41.62.837.2202

CT1

900-TC16P1V2

Regelausgang 2/

Stromwandler

12

11

15

14

13

900-TC16NCOMV2

Kommunikationen/

Regelausgang 2

B

A

RS-485

12

11

15

14

13

900-TC16NCOMP3

Kommunikationen/

Stromwandler 2

CT2

CT1

13

14

15

11

12

B

A

RS-485

900-TC16NACCOM

Kommunikationen

B

A

RS-485

12

11

15

14

13

900-TC16NACEIM

Ereigniseingänge

EV1

EV2

12

11

15

14

13

900-TC16NEIM

Ereigniseingänge /

Stromwandler

CT1

13

14

15

11

12

EV2

EV1

900-TC16NCOM

Kommunikationen/

Stromwandler

CT1

13

14

15

11

12

B

A

RS-485

Nicht
verwenden

Nicht
verwenden

Nicht
verwenden
Nicht
verwenden

Nicht
verwenden

Nicht
verwenden

Nicht
verwenden

Nicht

verwenden

Regelausgang 2

Regelausgang 2

Regelausgang 2

·

Spannungsausgang:

12 VDC, 21 mA

+

-

+

-

CT1

900-TC16P1V2
Sortie de contrôle 2/
CT

12

11

15

14

13

900-TC16NCOMV2
Communications/
Sortie de contrôle 2

B

A

RS-485

12

11

15

14

13

900-TC16NCOMP3
Communications/
CT2

CT2

CT1

13

14

15

11

12

B

A

RS-485

900-TC16NACCOM
Communication

Ne pas
utiliser
Ne pas
utiliser
Ne pas
utiliser

Ne pas
utiliser
Ne pas
utiliser

B

A

RS-485

12

11

15

14

13

900-TC16NACEIM
Entrées
événements

EV1

EV2

12

11

15

14

13

900-TC16NEIM
Entrées
événements / CT

CT1

13

14

15

11

12

EV2

EV1

900-TC16NCOM
Communication /
CT

CT1

13

14

15

11

12

B

A

RS-485

Ne pas
utiliser

Ne pas
utiliser

Ne pas
utiliser

Sortie de

contrôle 2

Sortie de
contrôle 2

Sortie de
contrôle 2

·

Voltage

outputs
DC12V
21mA

+

-

+

-

Allen-Bradley Company, LLC
Industrial Components Business
1201 South Second Street
Milwaukee, WI 53204-2496 USA
Phone 440.646.5800

Rockwell Automation
CH-5001 Aarau, Switzerland
FAX ++41.62.837.2202

Allen-Bradley Company, LLC
Industrial Components Business
1201 South Second Street
Milwaukee, WI 53204-2496 USA
Phone 440.646.5800

Rockwell Automation
CH-5001 Aarau, Switzerland
FAX ++41.62.837.2202

Temperature Controller
Option Units
900-TC16NCOM
900-TC16NEIM
900-TC16NACCOM
900-TC16NACEIM
900-TC16NCOMP3
900-TCNCOMV2
900-TC16P1V

English
41063-223-01 (2)
Printed In China

For detailed operating instructions, please
refer to the 900-TC16 User's Manual.
It can be found online at:
http://www.ab.com/manuals/.

Temperatur-Steuergerät
Optionseinheiten
900-TC16NCOM
900-TC16NEIM
900-TC16NACCOM
900-TC16NACEIM
900-TC16NCOMP3
900-TCNCOMV2
900-TC16P1V2

German
41063-223-01 (2)
Printed In China

For detailed operating instructions, please
refer to the 900-TC16 User's Manual.
It can be found online at:
http://www.ab.com/manuals/.

Contrôleur de température
Unités optionnelles
900-TC16NCOM
900-TC16NEIM
900-TC16NACCOM
900-TC16NACEIM
900-TC16NCOMP3
900-TCNCOMV2
900-TC16P1V2

French
41063-223-01 (2)
Printed In China

For detailed operating instructions, please
refer to the 900-TC16 User's Manual.
It can be found online at:
http://www.ab.com/manuals/.

FORM 981

A

B

C

D

E

F

H

G

1

2

3

4

5

6

7

8

1

2

TEMPERATURE CONTROLLER

OPTION UNITS

INSTRUCTION SHEET

1

1015641

2

1023125

G. Ushakow

6-9-06

M. Jutz

6-9-06

D. Schneider

6-9-06

41063-223

OF

.XX

.XXX

XX

REVISION

AUTHORIZATION

DR.

CHKD.

APPD.

DATE

DATE

DATE

E - DOC

LOCATION: MILWAUKEE, WISCONSIN U.S.A.

DWG.

SIZE

SHEET

C

REFERENCE

DIMENSIONS APPLY BEFORE

SURFACE TREATMENT

(DIMENSIONS IN INCHES)

TOLERANCES UNLESS

OTHERWISE SPECIFIED

.XX:

.XXX:

ANGLES:

41063

THIS DRAWING IS THE PROPERTY OF

ROCKWELL AUTOMATION, INC.

OR ITS SUBSIDIARIES AND MAY NOT BE COPIED,

USED OR DISCLOSED FOR ANY PURPOSE

EXCEPT AS AUTHORIZED IN WRITING BY

ROCKWELL AUTOMATION, INC.

C-horizontal.ai

Watertight packing

Wasserdichte Packung

Emballage étanche

Modell

Funktion

Kommunikation (RS-485)
Alarm für das Ausbrennen der Heizung, 1 Alarm (Stromwandler)
Ereigniseingänge, 2 Eingänge
Alarm für das Ausbrennen der Heizung, 1 Alarm (Stromwandler)
Kommunikation (RS-485)
Ereigniseingänge, 2 Eingänge
Kommunikation (RS-485)
Alarme für das Ausbrennen der Heizung, 2 Alarme (Stromwandler)
Kommunikation (RS-485)
Regelausgang 2 (Spannungsausgabe)
Regelausgang 2 (Spannungsausgabe)
Alarm für das Ausbrennen der Heizung, 1 Alarm (Stromwandler)

(1)

(5)

(2)

(1)

(3)

(4)

(1)

(5)

(2)

(1)

(3)

(4)

(1)

(5)

(2)

(1)

(3)

(4)