All parameters are specified at 12V, 4.5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
22
Rockwell Automation Publication 1606-RM015A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
20.12. Mounting Orientations
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in 
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction 
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous 
operation can be found below: 
Curve A1
Recommended output current.
Curve A2
Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 20-7
Mounting 
Orientation A 
(Standard 
orientation)
Power
Supply
OUTPUT
INPUT
Output Power
0
10
20
30
40
60°C
12
36
48
60W
50
A1
24
Ambient Temperature
Fig. 20-8
Mounting 
Orientation B 
(Upside down)
Power
Supply
OUTPU
T
INPUT
Output Power
0
10
20
30
40
60°C
12
36
48
60W
50
24
A1
A2
Ambient Temperature
Fig. 20-9
Mounting 
Orientation C 
(Table-top 
mounting)
Output Power
0
10
20
30
40
60°C
12
36
48
60W
50
24
A1
A2
Ambient Temperature
Fig. 20-10
Mounting 
Orientation D 
(Horizontal cw)
Power
Supply
OUTPUT
INPUT
Output Power
0
10
20
30
40
60°C
12
36
48
60W
50
24
A1
A2
Ambient Temperature
Fig. 20-11
Mounting 
Orientation E 
(Horizontal ccw)
Power Supply
OUTPUT
IN
PUT
Output Power
0
10
20
30
40
60°C
12
36
48
60W
50
24
A1
A2
Ambient Temperature