Daisy chaining outputs, Inductive and capacitive loads – Rockwell Automation 1606-XLP60BQT Power Supply Reference Manual User Manual
Page 19

All parameters are specified at 12V, 4.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM016A-EN-P — February 2014
19
Bulletin 1606 Switched Mode Power Supplies
20.6. Daisy Chaining Outputs
Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current
through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block.
Fig. 20-3 Daisy chaining of outputs
Fig. 20-4 Using distribution terminals
Power
Supply
+ +
- -
Input
Output
Load
+
-
max 25A!
Power
Supply
+ +
- -
Input
Output
Load
+
-
Distribution
Terminals
Power
Supply
+ +
- -
Input
Output
Power
Supply
+ +
- -
Input
Output
20.7. Inductive and Capacitive Loads
The unit is designed to supply any type of load, including unlimited capacitive and inductive loads.