Field calibration – Rockwell Automation 1414-ITXxxxxx_CTXxxxxx Duct Average Temperature Transmitter User Manual
Page 4

4 Duct Average-temperature Transmitter
Publication 1414-IN004B-EN-P - July 2010
Typical wiring to a controller is shown in the diagram. For 4…20 mA loop signal, only
the PWR and OUT terminals are used.
Field Calibration
The unit can be calibrated in the field by using precision resistor values equal to the zero and
span of the transmitter temperature range.
1. Disconnect the sensor from the transmitter and connect the resistor that represents the
zero value to the EXC and NEG terminals.
2. Adjust the ZERO pot until the desired output is achieved.
3. Connect the resistor that represents the span value to the EXC and NEG terminals.
4. Adjust the SPAN pot until the desired output is achieved.
Repeat these steps until no further adjustment is required.
TIP
If the unit uses a three-wire sensor, a jumper must be placed between EXC and
SEN.
NEG
EXC
SEN
PW
R
CO
M
OU
T
SPAN
ZERO
+ 24V DC -
ANL IN 0 +
ANL IN 0 -
Analog Current Input
ANL COM
Loop Power Supply
2-wire RTD
Sensor
Temperature Transmitter