Rockwell Automation 1494R-N16_N17_N18_N19 Lug Adapter Kit Installation Instructions User Manual
Rockwell Automation Equipment

Bulletin 1494R Lug Adapter Kit Installation Instructions
(Cat 1494R-N16, 1494R-N17, 1494R-N18, 1494R-N19)
(For use with Bulletin 1494C, 1494F, 1494G, 1494V Disconnect Switches)
To prevent electrical shock, disconnect from power source before installing or servicing,
Follow NFPA 70E requirements. Install in suitable enclosure. Keep free from contaminants.
Wire Clamp
Adapter
Wire Lug
Disconnect Switch
Lug Adapter Kit
Line and Load Lugs
Adapter
Torque
(Lb.-In.)
Catalog
Number
Catalog
Number
Wire
Clamp
Torque
(Lb.-In.)
Wire Lug
Torque
(Lb.-In.)
Wire Clamp
Wire Range
Wire Lug
Wire Range
Disconnect
Switch
Rating (Size)
Notes:
* 1. Assemble Washer beneath adapter for 30 amp. (See view)
1494R-N16
Included with
Switch
#14-#8 Cu,
Solid or
Stranded
#14-#4 Cu,
Solid or
Stranded
#8-#1/0 Cu,
Solid or
Stranded
#6-#4/0 Cu,
Solid or
Stranded
30A
25-28
1494R-N17
1494R-N1
1494R-N2
1494R-N3
60A
40-60
25
20
45
150
275
(1) 14-10 STR/SOL
(1) 8 STR
(2) 14 SOL/SOL
(2) 14 STR/STR
(2) 12 SOL/SOL
(2) 12 STR/STR
(2) 10 SOL/SOL
(2) 10 STR/STR
(2) 8 STR/STR
1494R-N18
100A
90-110
1494R-N19
200A / 400A
175-200
See Note 1
PN-43715
DIR 10000050673 (Version 02)
Printed in U.S.A.
2
1
WARNING