Rockwell Automation Publication 1606-RM001B-EN-P - August 2013

Bulletin 1606 Switched Mode Power Supplies

14. EMC

The power supply is suitable for applications in industrial environment as well as in residential, commercial and light industry environment without any
restrictions. A detailed EMC report is available on request.

Criterions:
A:

Power supply shows normal operation behavior within the defined limits.

C:

Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the power supply will occur.

*) tested with constant current loads, non pulsing
**)for information only, not mandatory for EN 61000-6-3

EMC Immunity

According generic standards: EN 61000-6-1 and EN 61000-6-2

Electrostatic discharge

EN 61000-4-2

contact discharge
air discharge

8kV
15kV

Criterion A
Criterion A

Electromagnetic RF field

EN 61000-4-3

80MHz-2.7GHz

20V/m

Criterion A

Fast transients (Burst)

EN 61000-4-4

input lines
output lines
DC-OK signal (coupling clamp)

4kV
2kV
2kV

Criterion A
Criterion A
Criterion A

Surge voltage on input

EN 61000-4-5

L

 N

L

 PE, N  PE

2kV
4kV

Criterion A
Criterion A

Surge voltage on output

EN 61000-4-5

+

 -

+ / -

 PE

1kV
2kV

Criterion A
Criterion A

Surge voltage on DC-OK

EN 61000-4-5

DC-OK signal

 PE

2kV

Criterion A

Conducted disturbance

EN 61000-4-6

0.15-80MHz

20V

Criterion A

Mains voltage dips

EN 61000-4-11

0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
70% of 200Vac

0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms

Criterion A
Criterion C
Criterion A
Criterion A
Criterion A
Criterion A

Voltage interruptions

EN 61000-4-11

0% of 200Vac (=0V)

5000ms

Criterion C

Voltage sags

SEMI F47 0706

dips on the input voltage according to SEMI F47 standard
80% of 120Vac (96Vac)
70% of 120Vac (84Vac)
50% of 120Vac (60Vac)

1000ms
500ms
200ms

Criterion A
Criterion A
Criterion A

Powerful transients

VDE 0160

over entire load range

750V, 1.3ms

Criterion C

EMC Emission

According generic standards: EN 61000-6-3 and EN 61000-6-4

Conducted emission
input lines

EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22

Class B

Conducted emission

output lines

**)

IEC/CISPR 16-1-2, IEC/CISPR 16-2-1

limits for DC power port according EN 61000-6-3
fulfilled

Radiated emission

EN 55011, EN 55022

Class B

Harmonic input current

EN 61000-3-2

fulfilled for class A equipment

Voltage fluctuations, flicker

EN 61000-3-3

fulfilled

*)

This device complies with FCC Part 15 rules.

Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including
interference that may cause undesired operation.

Switching Frequencies

The power supply has two converters with two different switching frequencies included.

Switching frequency 1

70kHz to 130kHz

PFC converter, input voltage and output power dependent

Switching frequency 2

80kHz to 140kHz

Main converter, output power dependent