Bypass switch wiring diagram, Circuit breaker recommendations, Accessing prodysc terminations – Rockwell Automation 1608P ProDySC Installation Instructions, 25 and 50 A User Manual
Page 11
Rockwell Automation Publication 1608P-IN001B-EN-P - May 2014
11
Installation
Chapter 2
Bypass Switch
Wiring Diagram
The maintenance bypass has input and output terminals labeled and located 
inside the bypass enclosure as shown in 
Figure 5
. The neutral connection is
available for 4-wire ProDySC configurations.
NOTICE: All electrical connections must be completed by a qualified electrician, in compliance 
with all local codes and the National Electric Code.
Figure 5 - Bypass wiring diagram
Circuit Breaker 
Recommendations
Branch circuit protection upstream of the ProDySC is required. Recommended 
circuit breakers and maximum allowed circuit breaker ratings are listed in 
Table 1
. Branch circuit protection rated less than the ProDySC current rating
may result in nuisance tripping.
Table 1 - Recommended Branch Circuit Protection
Accessing ProDySC 
Terminations
Two holes are provided for punch-out locations to provide the appropriate hole 
size for conduit fittings in the ProDySC. Take care to avoid dropping any metal 
filings inside the enclosure. Metallic contamination will void the product 
warranty. See 
Figure 6
for preferred Input/Output wiring locations.
Figure 6 - Knockout Hole Locations
ProDySC Rating
Recommended MCCB
Cat. No.
Max. MCCB Rating
25 A
140U-H3C3-C35
35 A
50 A
140U-H6C3-C70
70 A
2X 1.12
28
TOP VIEW