Output – Rockwell Automation 1606-XLS960E-3 Power Supply Reference Manual User Manual

Page 6

Advertising
background image

All parameters are specified at 24V, 40A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

6

Rockwell Automation Publication 1606-RM005A-EN-P - February 2014

Bulletin 1606 Switched Mode Power Supplies

6. Output

Output voltage

nom.

24V

Adjustment range

min.

24-28V

guaranteed

max.

30V

***)

at clockwise end position of potentiometer

Factory setting

typ.

24.1V

±0.2%, at full load, cold unit, in “single use” mode

typ.

24.1V

±0.2%, at full load, cold unit, in “parallel use” mode

typ.

25.1V

at no load, cold unit, in “parallel use” mode

Line regulation

max.

10mV

3x323-576Vac

Load regulation

max.

50mV

in “single use” mode: static value, 0A 40A, see Fig. 6-1

typ.

1000mV

in “parallel use” mode: static value, 0A 40A,
see Fig. 6-2

Ripple and noise voltage

max.

100mVpp

20Hz to 20MHz, 50Ohm

Output current

nom.

40A

continuously available at 24V, see Fig. 6-1 and Fig. 6-2

nom.

34.3A

continuously available at 28V, see Fig. 6-1 and Fig. 6-2

nom.

60A

short term (4s) available BonusPower

*)

, at 24V,

see Fig. 6-1, Fig. 6-2 and Fig. 6-4

nom.

51.5A

short term (4s) available BonusPower

*)

, at 28V,

see Fig. 6-1, Fig. 6-2 and Fig. 6-4

typ.

110A

up to 25ms, output voltage stays above 20V, see Fig.
6-4. This peak current is available once every second.
See section 25.2 for more peak current measurements.

Output power

nom.

960W

continuously available at 24-28V

nom.

1440W

*)

short

term

available

BonusPower

*)

at 24-28V

BonusPower

time

typ.

4s

duration until the output voltage dips, see Fig. 6-3

BonusPower

recovery time

typ.

7s

overload free time to reset power manager, see Fig. 6-5

Overload behavior

cont. current

see Fig. 6-1

Short-circuit current

**)

min.

40A

continuous, load impedance 25mOhm, see Fig. 6-1

max.

44A

continuous,

load

impedance

25mOhm,

see

Fig.

6-1

min.

60A

short-term (4s), load impedance 25mOhm, see Fig. 6-1

max.

68A

short-term (4s), load impedance 25mOhm, see Fig. 6-1

typ.

46A

continuous, load impedance <10mOhm

max.

51A

continuous, load impedance <10mOhm

Output capacitance

typ.

10 200μF

included in the power supply

*)

BonusPower, short term power capability (up to typ. 4s)

The power supply is designed to support loads with a higher short-term power requirement without damage or shutdown. The short-
term duration is hardware-controlled by an output power manager. BonusPower is repeatedly available. Detailed information

can be found in section 25.1. If the power supply is loaded longer with the BonusPower

than shown in the bonus-time diagram (see

Fig. 6-3), the max. output power is automatically reduced to 960W.

**)

Discharge current of output capacitors is not included.

***)

This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. There is no
guarantee that this value can be achieved. The typical value is about 28.5V.

Advertising