Field adjustment, Specifications – Rockwell Automation 1414-CPNxxxxx_CPMxxxxx Air Flow Switch User Manual

Page 4

Advertising
background image

4 Air Flow Switch

Publication 1414-IN003A-EN-P - October 2005

Figure 2 Alarm or Control

Field Adjustment

From lowest operating point several turns of the adjusting screw are necessary to
engage the calibration spring. No change in set point will occur until the spring is
engaged. For higher set points continue turning screw in a clockwise direction. It
may be useful to connect a manometer in parallel with the switch when adjusting,
as the final operating point can be noted for future reference. Please see
specifications for actual ranges and set point information.

Specifications

Air Flow Switch Specifications

Specification

1414-CPN10APWAB

1414-CPN10APQAB

1414-CPM10APWAB

Sample Media

Air

Air

Air

Mounting Position

Diaphragm in any vertical
plane

Diaphragm in any
vertical plane

Diaphragm in any
vertical plane

Field Adjustable
Range

.05, ±.02” w.c. to 12” w.c.

.05, ±.02” w.c. to 2” w.c.

.40, ±.06” w.c. to 12” w.c

Switch Differential

Progressive, increasing
from approximately .02±
.01” w.c. at minimum set
point, to approximately .8”
w.c. at maximum set point.

Progressive, increasing
from 0.02± 0.01” w.c. at
minimum set point to
approximately 0.1” w.c.
at maximum set point.

Progressive, increasing
from approximately .06±
.01” w.c. at minimum set
point, to approximately
.8”w.c. at maximum set
point.

Maximum Pressure

.5” (0.03 bar)

.5” (0.03 bar)

.5” (0.03 bar)

Operating
Temperature Range

-40°C … 82.2°C
(-40°F…180°F)

-40°C … 82.2°C
(-40°F…180°F)

-40°C … 82.2°C
(-40°F…180°F)

C

C

NO

NC

NC

NO

Alarm

Control

Control

Alarm

To prove excessive airflow or pressure

To prove insufficient airflow or pressure