2

Wiring and Connecting the UPS

C

ONNECTING

UPS

USING POWER CORD

:

3000VA

U

NITS

1609-P3000N – Use captive 8 ft cord. NEMA L5-30 Plug is attached to this cord.

1609-P3000H – Use in captive 8 ft cord. NEMA L6-30 Plug is attached to this cord.

1609-P3000A – User must supply power cord. Power cord must mate with IEC 320 C20 inlet.

H

ARDWIRING

I

NSTRUCTIONS

:

1609-P5000E

• Wiring must be performed by a qualified electrician.
• Install a high magnetic 30/32 A utility circuit breaker (Allen-Bradley Catalog Number 1489-A2C300).
• Adhere to all national and local electrical codes.
• Use #10 AWG gauge (5 sq. mm) wire.

1. Switch the utility circuit breaker OFF.
2. Remove the input access panel.
3. Remove circular knockout.

4. Run #10 AWG gauge (5 sq. mm) wire through the access panel, and connect the wires to the terminal block

(Green: Ground, Brown: Hot, Blue: Neutral). Use an appropriate strain relief (not included).

5. Switch the utility circuit breaker ON.
6. Check line voltages.
7. Replace the access panel.